Rockwell Automation 6012DB PowerFlex Medium Voltage Variable Frequency Drive User Manual
Page 59

Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
59
Parameters and Function Codes
Chapter 4
P232
Filter Time For Overspeed Fault (Lower Limit)
100
ON
0
32767
P233
Threshold Of Over-Speed Fault At Lower Frequency Limit 20
ON
0
199.99
P234
Threshold Of Over-Speed Fault At Upper Frequency Limit 20
ON
0
199.99
P235
Frequency Deviation Warning Cancellation Threshold
0.99
ON
0
199.99
P236
Frequency Deviation Warning Threshold
6
ON
0
199.99
P237
Frequency Deviation Warning Delay (ms)
8
ON
0
32767
P238
Motor Stall Fault Threshold
10
ON
0
199.99
P239
Motor Stall Fault Delay (ms)
6000
ON
0
32767
P240
Transformer Over Temperature Fault Delay (ms)
5000
ON
0
32767
P241
Transformer Over Temperature Warning Delay (ms)
5000
ON
0
32767
P247
Software Interlock: 1-Disable, 0-Enable
1
ON
0
1
P250
Input Contactor/Circuit Breaker Close Delay (ms)
5000
ON
0
10000
P251
Frequency Command-Low Frequency Region Boundary
0.5
ON
0
100
P252
Motor In Stopping Condition Threshold
1
ON
0
100
P253
Motor Coast Stop Time
10
ON
0
10000
P256
Ground Fault Warning Cancellation Threshold
10
ON
0
199.99
P257
Motor Stall Warning Cancellation Threshold
2.98
ON
0
199.99
P259
Frequency Command Analog Offset
0
ON
-100
199.99
P260
Frequency Command Analog Scaling Factor
100
ON
0
199.99
P261
Frequency Command Analog Minimum
0.49
ON
0
199.99
P262
Frequency Command Source Selection: 0-Digital, 1-
Analog
0
OFF
0
1
P270
Delayed Lockout Time Of Stop Operation (ms)
2000
ON
0
5000
P271
Flux Delay (ms)
50
ON
0
5000
P300
Digital Output #0 Memory Address
99
ON
0
500
P301
Digital Output #0 Logic: 1-Inverting, 0-Non-Inverting
0
ON
0
1
P302
Digital Output #0 Bit Selection (0...15)
0
ON
0
15
P303
Digital Output #0 Delay (ms)
0
ON
0
32767
P304
Digital Output #1 Memory Address
99
ON
0
500
P305
Digital Output #1 Logic: 1-Inverting, 0-Non-Inverting
0
ON
0
1
P306
Digital Output #1 Bit Selection (0...15)
1
ON
0
15
P307
Digital Output #1 Delay (ms)
0
ON
0
32767
P308
Digital Output #2 Memory Address
99
ON
0
500
P309
Digital Output #2 Logic
1: Inverting
0: Non-Inverting
0
ON
0
1
P310
Digital Output #2 Bit Selection (0...15)
2
ON
0
15
P311
Digital Output #2 Delay (ms)
0
ON
0
32767
P312
Digital Output #3 Memory Address
99
ON
0
500
Parameter
Number
Description
Default
Value
Modify
Root
Lower
Limit
Upper
Limit