Rockwell Automation 6012DB PowerFlex Medium Voltage Variable Frequency Drive User Manual
Page 58

58
Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Chapter 4
Parameters and Function Codes
P090
Skip Frequency 1 Lower Limit
0
ON
0
75
P091
Skip Frequency 1 Upper Limit
0
ON
0
75
P092
Skip Frequency 2 Lower Limit
0
ON
0
75
P093
Skip Frequency 2 Upper Limit
0
ON
0
75
P113
Flying Start-Initial Output Voltage Percentage (%)
5
ON
0
100
P114
Flying Start-Current Comparison Delay For Motor Speed
Search (ms)
1000
ON
0
5000
P115
Flying Start-Current Threshold For Successful Motor
Speed Search
5
ON
0
100
P198
HECS Rated Current (A)
0
ON
0
5000
P199
Motor Rated Current (A)
0
ON
0
5000
P200
Ia Motor Current Memory Address
13
ON
0
500
P201
Motor Ia Scaling Correction Factor
100
ON
0
199.99
P202
Ib Motor Current Memory Address
14
ON
0
500
P203
Motor Ib Scaling Correction Factor
100
ON
0
199.99
P204
Motor Uab Voltage Address
11
ON
0
500
P205
Motor Uab Voltage Scaling Factor Correction
199.99
ON
0
199.99
P206
Motor Uac Voltage Scaling Factor Correction
199.99
ON
0
199.99
P211
Filter Time For Abnormal Output Voltage (ms)
1000
ON
0
32767
P212
Filter Time For Output Short-Circuit (ms)
10
ON
0
32767
P213
Output Short-Circuit Fault Threshold
180
ON
0
199.99
P214
Over Current Low/High Speed Region Boundary
5
ON
0
100
P215
Filter Time For Output Over Current (0.1 s)
200
ON
0
32767
P216
High-Frequency Output Over Current Threshold
120
ON
0
199.99
P217
Low-Frequency Output Over Current Threshold
70
ON
0
199.99
P218
Filter Time For Motor Over Temperature (0.1 s)
6000
ON
0
32767
P219
Motor Over Temperature Warning Threshold
110
ON
0
199.99
P220
Motor Over Temperature Fault Threshold
120
ON
0
199.99
P221
Filter Time For Output Over Voltage (ms)
100
ON
0
32767
P222
Output Over Voltage Fault Threshold
130
ON
0
199.99
P223
Output Voltage Deviation Warning Threshold
60
ON
0
199.99
P224
Output Voltage Deviation Fault Threshold
80
ON
0
199.99
P225
Motor Over Temperature Warning Cancellation
Temperature
100
ON
0
199.99
P226
Output Voltage Abnormality Warning Cancellation
Threshold
50
ON
0
199.99
P227
Ground Fault Detection Scaling Correction Factor
100
ON
0
199.99
P228
Filter Time For Ground Fault (ms)
1000
ON
0
32767
P229
Ground Fault Warning Threshold
20
ON
0
199.99
P230
Ground Fault Trip Threshold
60
ON
0
199.99
P231
Filter Time For Overspeed Fault (Upper Limit)
100
ON
0
32767
Parameter
Number
Description
Default
Value
Modify
Root
Lower
Limit
Upper
Limit