Running Applications
Publication 2706–816
Send data to a display variable with [Ctrl-V]
Used by the ASCII Triggering device to send data to a specific
display variable. Each variable must be addressed individually.
Numeric data may be scaled.
Format: [Ctrl-V]Variable Data\ Variable Position\ MV Address[CR]
•
Variable Data range: –32768 to +65535 for numeric data
any ASCII character for ASCII data
•
Variable Position range: 1 to 10
Note: Variable position is the position of the variable in the
message, counting from left to right. If the message contains only
one display variable, the position is 1.
•
MV Address range: 1 to 127 for a single node; 127 to address all
devices
Data enclosed in quotation marks is interpreted as ASCII data, even
if it consists of numbers.
Example: [Ctrl-V]“Press “ACK””\ 1\ 2[CR]
•
The terminal at node #2 displays Press “ACK” in the first
display variable in the currently active message.
Activate/Deactivate an LED with [Ctrl-L]
Used by the ASCII Triggering device to toggle a specific LED.
•
Format: [Ctrl-L]LED#\ LED State\ MV Address[CR]
•
LED# range: 1 to 16
•
LED State range 0 or 1; 0 represents the LED Off state, 1
represents the LED On state
•
MV Address range: 1 to 127 for a single node; 127 to address all
devices
Example: [Ctrl-L]4\ 1\ 22[CR]
•
The terminal at node #22 turns LED #4 On.
Unlatch a latched function key with [Ctrl-U]
Used by the ASCII Triggering device to unlatch a specific latched
function key.
Format: [Ctrl-U]F-key#\ MV Address[CR]
•
F-key# range: 1 to 16
•
MV Address range: 1 to 127 for a single node; 127 to address all
devices