6–15

Remote I/O and RS-232 Connections

Publication 2706–816

A MessageView terminal (Catalog No. 2706-M1D1, -M1N1,
-M1F1) connects to any Allen-Bradley 1771 Remote I/O link.
Applicable host controllers are listed in the table below

When connecting a MessageView terminal to a controller, refer to
the user manual for the controller or scanner module for connection
diagrams and any Remote I/O limitations. The table below provides
a list of compatible controllers/scanners.

Controllers and Scanners Compatible with MessageView
Terminals

Controller

Subscanner

Comments

PLC-5

/11,

5/15➀, 5/20, 5/25,

PLC Integral

Connect MessageView terminals directly to the
Remote I/O port (scanner mode).

5/15 , 5/20, 5/25,
5/30, 5/40, 5/60,
5/80, 5/250

1771-SN

Connect MessageView terminals through the
1771-SN Subscanner Module.

PLC-5/10, 5/12

1771-SN

Connect MessageView terminals through the
1771-SN Subscanner Module.

P C 3

and

None

Connect MessageView terminals directly to a
PLC-3.

PLC-3

and

PLC-3/10

PLC 3/10

Remote I/O

Scanner➁

Connect MessageView terminals to the PLC-3/10
through the Remote I/O scanner.

PLC-2

1771–SN or

1772-SD2➃

Connect MessageView terminals to the PLC-2
family of processors through a 1771-SN I/O
Subscanner Module or 1772-SD2
Scanner/Distribution panel.

SLC-5/02, 5/03

t,

5/04

t

1747-SN

Connect MessageView terminals through the
1747-SN Subscanner Module. Each Subscanner
Module provides an additional Remote I/O link for
up to 4 racks.
Important: Only Series B and later versions of the
1747-SN subscanner support block transfers.

IBM PC

6008-SI

6008-SI I/O Scanner is compatible with IBM PC or
compatible personal computers. The scanner
provides a personal computer access to the 1771
Remote I/O link.

VME

t

6008-SV

6008-SV I/O Scanner provides access to the 1771
Remote I/O link for VME controllers.

DEC Q-BUS

t

6008-SQ

6008-SQ I/O Scanner provides access to the 1771
Remote I/O link for DEC Q-BUS controllers.

If you use a PLC-5/15 with partial rack addressing and block transfers, you must use Series B,
Rev. J or later.

If you use a 1775-S4A Remote Scanner/Distribution Panel, you must use Series B or later.

If you use a PLC-2 be sure to consult the manual on proper addressing.

If you use a 1772-SD2 Remote Scanner/Distribution Panel, you must use revision 3 or later.

Compatible Controllers