beautypg.com

Rockwell Automation 6186M-xxxx Industrial Performance Monitors User Manual User Manual

Page 16

background image

16

Rockwell Automation Publication 6186M-UM002B-EN-P - March 2012

Chapter 2

Installing the Monitor

Control Drawing - Class I Division 2 and Zone 2 (USB port, type B)

The following control drawing is provided to comply with the National Electrical
Code, Article 500 pertaining to Class I, Division 2, Groups A, B, C, D and Class
I, Zone 2, Group IIC.

Figure 2 - Industrial Performance Monitors USB Port, Type B

Table 3 - Required Circuit Parameters for USB, Type B, Connector - Connecting to Host

Parameter

Value

Parameter Definition

V

Bmax (USB)

5.25V DC, max

Maximum applied voltage rating of the 6186M USB Type B connector. The
output of the host product shall not exceed this value.
V

Bmax (USB)

V

OC (Host USB)

I

Bmax (USB)

110 μA, min

Maximum current required at the 6186M USB Type B connector. The host
product must be capable of a minimum of this value.
I

SC (Host USB)

 I

Bmax (USB)

C

iB (USB)

0 μF

Total capacitance of the 6186M USB Type B connector. The host product must be
capable of tolerating this value of capacitance.
C

a (Host USB)

C

iB (USB)

+ C

cable

L

iB (USB)

0 μH

Total Inductance of the 6186M USB Type B connector. The host product must be
capable of tolerating this value of inductance.
L

a (Host USB)

L

iB (USB)

+

L

cable

6186M Hub Product

Associated
Field-wiring Apparatus

Nonincendive
Field-wiring Apparatus

Host Product

USB Port, Type B

USB Port, Type B