Page a-4 – Rockwell Automation 2090 Ultra3000 Installation Manual User Manual
Page 9
Publication 2098-DU003B-EN-P — September 2006
Ultra3000 Digital Servo Drive Installation Manual
5
Page A-4
Add the attention statement (below) to the Ultra3000 (460V) Power
Specifications table on page A-4. The table didn’t change, however,
the warning applies to all Ultra3000 drives.
Ultra3000 Drive (460V) Power Specifications
2098-DSD-HV030x-xx, -HV050x-xx, -HV100x-xx, -HV150x-xx, and -HV220x-xx
Specification
Description
2098-DSD-HV030
2098-DSD-HV050
2098-DSD-HV100
2098-DSD-HV150
2098-DSD-HV220
AC Input Voltage
(1) (2)
230...480V rms
Three-phase
AC Input Frequency
47...63 Hz
Main AC Input Current
(3) (4)
460V ac (rms) Nom
460V ac (rms) Max inrush
4 A
6 A
7 A
6 A
14 A
6 A
20 A
6 A
28 A
6 A
Auxiliary AC Input Current
230V ac (rms) Nom
360V ac (rms) Nom
480V ac (rms) Nom
230V ac (0-pk) Max inrush
(5)
480V ac (0-pk) Max inrush
(5)
0.55 A
0.35 A
0.25 A
47 A
68 A
Continuous Output Current (0-pk)
7 A
11 A
23 A
34 A
47 A
Intermittent Output Current (0-pk)
14 A
22 A
46 A
68 A
94 A
Bus Capacitance
470 μF
705 μF
940 μF
1880 μF
Internal Shunt Resistance
120
Ω
40
Ω
25
Ω
20
Ω
Shunt On
800V dc
Shunt Off
750V dc
Bus Overvoltage
810V dc
Internal Shunt
Continuous power
Peak power
100 W
5.3 kW
200 W
16 kW
200 W
25.6 kW
400 W
32 kW
External Shunt
Resistance (-0/+5%)
Continuous power
Peak power
120
Ω
3 kW
5.3 kW
40
Ω
10 kW
16 kW
25
Ω
15 kW
25.6 kW
20
Ω
22 kW
32 kW
Energy Absorption Capability
230V ac input with 230V motor
230V ac input with 460V motor
460V ac input
15 J
129 J
55 J
22 J
194 J
82 J
29 J
259 J
109 J
59 J
517 J
219 J
Continuous Power Output
230V ac input
460V ac input
1.5 kW
3.0 kW
2.5 kW
5.0 kW
5.0 kW
10 kW
7.5 kW
15 kW
11 kW
22 kW
(1)
Specification is for nominal voltage. The absolute limits are ±10%, or 207...528V rms.
(2)
The 2098-DSD-HVxxx-xx drives can be powered with 230-240 V rms in order to be used in conjunction with motors designed for 230V operation. In such cases, the voltage
levels used for shunting and DC bus overvoltage limits are adjusted to be compatible with the voltage limit of the motor.
(3)
The 2098-DSD-HVxxx -xx (460V) drives are limited to three contactor cycles per minute.
(4)
Power initialization requires a short period of inrush current (processor controlled via soft start circuitry). Dual element time delay (slow blow) fuses are recommended
(refer to Fuse Specifications on page 6-8).
(5)
400
μs half wave sine.
ATTENTION
The inrush current-limiting circuitry is limited in the number of
power cycles it can withstand within a set period of time. If you
exceed these limitations, the circuitry will be damaged.