Fuse specifications – Rockwell Automation 2090 Ultra3000 Installation Manual User Manual
Page 143
Publication 2098-IN003E-EN-P — April 2004
Specifications and Dimensions
A-5
Fuse Specifications
Use class CC, G, J, L, R, or T class fuses, with current ratings as
indicated in the table below. The table below lists fuse examples
recommended for use with the Ultra3000 (230V and 460V) drives.
Refer to Power Wiring Requirements in Chapter 3 for input wire size.
1
Bussmann
®
Fuse
Catalog Number
Input
Voltage
Voltage Type
Recommended Fuse
Class CC
1
Class J
1
2098-DSD-005x-xx
230V
Input Power
FNQ-R-6
LPJ-6SP
2098-DSD-010x-xx
FNQ-R-10
LPJ-10SP
2098-DSD-020x-xx
FNQ-R-20
LPJ-20SP
2098-DSD-030x-xx
FNQ-R-30
LPJ-30SP
2098-DSD-075x-xx
FNQ-R-30
LPJ-30SP
2098-DSD-150x-xx
N/A
LPJ-60SP
2098-DSD-xxxx-xx
Auxiliary Input Power
FNQ-R-10
LPJ-10SP
2098-DSD-HV030x-xx
460V
Input Power
KTK-R-5
LPJ-5SP
2098-DSD-HV050x-xx
KTK-R-8
LPJ-8SP
2098-DSD-HV100x-xx
KTK-R-20
LPJ-17-1/2SP
2098-DSD-HV150x-xx
KTK-R-30
LPJ-30SP
2098-DSD-HV220x-xx
N/A
LPJ-35SP
2098-DSD-HVxxxx-xx
Auxiliary Input Power
FNQ-R-10
LPJ-10SP
IMPORTANT
Follow the wire size information as shown in the
Power Wiring Requirements table on page 3-13 and
select the fuse for the appropriate temperature rating
of the wire. Auxiliary input fuses must not exceed
13A.