Specifications and Dimensions

A-7

Contactor Ratings

The table below lists contactor examples recommended for use with
the Ultra3000 (460V) drives.

Power Dissipation Specifications

Use the following table to size an enclosure and calculate required
ventilation for the Ultra3000. Typical heat losses run approximately
one-half maximum power losses. The maximum power losses are
shown below.

Catalog Number

Input
Voltage

Contactor

2098-DSD-HV030x-xx

460V

100-C23x10 (AC Coil)

100-C23Zx10 (DC Coil)

2098-DSD-HV050x-xx

100-C30x10 (AC Coil)

100-C30Zx10 (DC Coil)

2098-DSD-HV100x-xx

100-C37x10 (AC Coil)

100-C37Zx10 (DC Coil)

2098-DSD-HV150x-xx

100-C43x10 (AC Coil)

100-C43Zx10 (DC Coil)

2098-DSD-HV220x-xx

100-C60x10 (AC Coil)

100-C60Zx10 (DC Coil)

Catalog Number

Maximum Loss
Watts

Catalog Number

Maximum Loss
Watts

2098-DSD-005x-xx

48 2098-DSD-HV030x-xx

175 + dissipative shunt

2098-DSD-010x-xx

48

2098-DSD-HV050x-xx

175 + dissipative shunt

2098-DSD-020x-xx

50

2098-DSD-HV100x-xx

350 + dissipative shunt

2098-DSD-030x-xx

150 + dissipative shunt

2098-DSD-HV150x-xx

350 + dissipative shunt

2098-DSD-075x-xx

300 + dissipative shunt

2098-DSD-HV220x-xx

600 + dissipative shunt

2098-DSD-150x-xx

500 + dissipative shunt

This manual is related to the following products: