Connecting your devicenet cable – Rockwell Automation 2090 Ultra3000 Installation Manual User Manual
Page 126
Publication 2098-IN003E-EN-P — April 2004
3-30
Connecting Your Ultra3000
Connecting Your DeviceNet Cable
To wire the DeviceNet connector:
1. Strip 65 mm (2.6 in.) to 75 mm (2.96 in.) of the outer jacket from
the end of the cable, leaving no more than 6.4 mm (0.25 in.) of
the braided shield exposed.
Figure 3.25
Exposing the Braided Shield
2. Wrap the end of the cable with 38 mm (1.5 in.) of shrink wrap,
covering part of the exposed wires and part of the outer jacket.
Figure 3.26
Adding Shrink Wrap
3. Strip 8.1 mm (0.32 in.) of the insulation from the end of each of
the insulated wire.
Trim the last 6.4 mm (0.25 in.) of the bare wires so that the outside
dimension does not exceed 0.17 mm (0.045 in.).
Figure 3.27
Exposing Wire Strands
IMPORTANT
Use caution not to nick, cut, or otherwise
damage strands as you remove the insulation.
6.4 mm
(0.25 in.)
65 mm
(2.6 in.)
Outer Jacket
Braided Shield
38 mm
(1.5 in.)
Outer Jacket
Shrink Wrap
8.1 mm
(0.32 in.)
Outer Jacket
Shrink Wrap