Rockwell Automation 1790P-T4T0 CompactBlock LDX I/O Thermocouple Modules User Manual

Page 94

background image

Publication 1790-UM003A-EN-P

E-6 Module Configuration for PROFIBUS

Select the
temperature units
(°C or °F). All four
channels will be
configured identically.

Select the filter cutoff
frequency desired. All
four channels will be
configured identically.

Select to enable (auto)
or disable (manual)
built-in cold junction
compensation.

If built-in CJC is
disabled, you can
enter a constant
cold junction
offset value. The
value is always
entered in °C.
The range is 0 to
70°C (000 to 700).

70°C is entered as 7000
(158°F as 700 also).