Rockwell Automation 1790P-T4T0 CompactBlock LDX I/O Thermocouple Modules User Manual

Page 48

background image

Publication 1790-UM003A-EN-P

3-18 Module Data, Status, and Channel Configuration for DeviceNet

Select to Enable or
Disable built-in cold
junction compensation.

If built-in CJC is
disabled, you can
enter a constant cold
junction offset value.
The value is always
entered in °C. The
range is 0 to 70°C
(000 to 700).

70°C is entered as 700
(158°F as 700 also).

Once module configuration is
complete, click either the
Download or Apply button
and click Yes for the popup
question.

Then click OK to close the
module properties window.