Appendix a, specifications, Environmental specifications, Appendix a – Rockwell Automation 1790P-T4T0 CompactBlock LDX I/O Thermocouple Modules User Manual
Page 57: Specifications, Appendix
![background image](/manuals/579687/57/background.png)
1
Publication 1790-UM003A-EN-P
Appendix
A
Specifications
Environmental
Specifications
Environmental Specifications
Operating Temperature
0 to 55°C (32 to 131°F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Storage Temperature
-40 to 85°C (-40 to 185°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock)
Relative Humidity
5-90% non-condensing
IEC 60068-2-30 (Test Db, Un-packaged Non-operating)
Operating Altitude
2000m
Vibration
I2g @ 10-500Hz
EC60068-2-6 (Test Fc, Operating)
Shock: Operating
Non-operating
I0g
30g
IEC60068-2-27 Test Ea, (Unpackaged Shock, ES#002)
Emissions
Group 1, Class A
CISPR 11
ESD Immunity
8kV air discharges
IEC 61000-4-2
Radiated RF Immunity
10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz
10V/m with 200Hz 50% Pulse 100%AM @ 900Mhz
IEC 61000-4-3
EFT/B Immunity
+1kV @ 5kHz on power ports
+2kV @ 5kHz on signal ports
+2kV @ 5kHz on communications ports
IEC 61000-4-4
Surge Transient
Immunity
+1kV line-line(DM) and +2kV line-earth(CM) on power ports
+1kV line-line(DM) and +2kV line-earth(CM) on signal ports
+2kV line-earth(CM) on shielded ports
IEC 61000-4-5
Conducted RF Immunity 10Vrms with 1kHz sine-wave 80%AM from 150kHzto 80MHz
IEC 61000-4-6
Enclosure Type Rating
None (open style)
Mounting
DIN rail or screw
Dimensions
52 x 104 x 42mm (2.03 x 4.07 x 1.64in)
Weight
0.3lb (0.1kg)