Module operation - devicenet example -5, Module operation - devicenet example – Rockwell Automation 1790P-T4T0 CompactBlock LDX I/O Thermocouple Modules User Manual

Page 13

background image

Publication 1790-UM003A-EN-P

Overview 1-5

Module Operation - DeviceNet Example

When the module recieves a differential input from an analog device, the
module’s circuitry multiplexes the input into an A/D converter. The
converter reads the signal and converts it as required for the type of input.
The module also continuously samples the CJC sensors and compensates
for temperature changes at the terminal block cold junction, between the
thermocouple wire and the input channel. See the block diagram below.

Figure 1.3 Block Diagram

Each channel can receive input signals from a thermocouple or millivolt
analog input device, depending upon how you configured the channel.

When configured for thermocouple input types, the module converts the
analog input voltages into cold-junction compensated and linearized
digital temperature readings. The module uses the National Institute of
Standards and Technology (NIST) ITS-90 standard for linearization for all
thermocouple types (J, K, T, E, R, S, B, N).

When configured for millivolt inputs, the module converts the analog
values directly into digital counts.

Input

CH0

Multiplexer

VA2

A/D

VREF

Vref

Channel Select

Channels 1 through 3 same as
channel 0 above.

43309

A

B

VA1

Vcc

Optical
Isolation

AIN-

AIN+1

VA3

A-GND

Micro-
Controller

Transmit

Receive

GND

Network

Power

Supply

Analog
Power
Supply

DeviceNet
24Vdc
Power

Vcc

GND

VA1

VA2

VA3

A-GND

VDC

GND

1

2

3

Auxiliary
24Vdc
Power

Transceiver

+

_