1769-if8 input module addressing, 1769-if8 input module addressing -16 – Rockwell Automation 1769-OF2 Compact I/O Analog Modules User Manual
Page 66

Publication 1769-UM002B-EN-P - July 2005
3-16 Module Data, Status, and Channel Configuration for the Input Modules
1769-IF8 Input Module
Addressing
The1769-IF8 memory map shows the output, input, and configuration tables
for the 1769-IF8.
Figure 3.4 1769-IF8 Memory Map
slot e
Input Image
File
Output Image
File
Configuration
File
slot e
slot e
Input Image
12 words
Output Image
1 word
Configuration File
50 words
Memory Map
Bit 15
Bit 0
Channel 6 Configuration Words
Words 38-43
Channel 5 Configuration Words
Words 32-37
Channel 4 Configuration Words
Words 26-31
Channel 3 Configuration Words
Words 20-25
Channel 2 Configuration Words
Words 14-19
Channel 1 Configuration Words
Words 8-13
Channel 0 Configuration Words
Words 2-7
Clear Latched Alarm Bits
Word 0
High-/Low-Alarm & Over-/Under-Range
Word 10
General Status Bits
Word 9, bits 0-7
Time Stamp Value Word
Word 8
Channel 7 Data Word
Word 7
Channel 6 Data Word
Word 6
Channel 5 Data Word
Word 5
Channel 4 Data Word
Word 4
Channel 3 Data Word
Word 3
Word 2
Channel 2 Data Word
Word 1
Channel 1 Data Word
Channel 0 Data Word
Word 0
Channel 7 Configuration Words
Words 44-49
Enable Time Stamp
Word 1, bit 15
Real Time Sample Rate
Word 0
High-/Low-Alarm & Over-/Under-Range
Word 11