Rockwell Automation 1769-OF2 Compact I/O Analog Modules User Manual

Page 109

background image

Publication 1769-UM002B-EN-P - July 2005

Module Data, Status, and Channel Configuration for the Output Modules 4-27

Table 4.15 1769-OF8C Output Range/Types and Output Data Formats

Output Data
Format Output
Range/Type

Total Counts in
Full Scale

Number of Counts
for Every 1% of
Ramp Rate

Real Units/Second
for Every 1% of
Ramp Rate

Proportional Counts

0…20 mA

65534

655

0.2 mA/s

4…20 mA

0.16 mA/s

Engineering Units

0…20 mA

21000

210

0.2 mA/s

4…20 mA

17800

178

0.16 mA/s

Scaled for PID

0…20 mA

16383

164

0.2 mA/s

4…20 mA

0.16 mA/s

Percent of Full Scale

0…20 mA

10000

100

0.2 mA/s

4…20 mA

0.16 mA/s

Table 4.16 1769-OF8V Output Range/Types and Output Data Formats

Output Data
Format Output
Range/Type

Total Counts in
Full Scale

Number of Counts
for Every 1% of
Ramp Rate

Real Units/Second
for Every 1% of
Ramp Rate

Proportional Counts

-10…+10V

65534

655

0.2V/s

0…5V

0.05V/s

0…10V

0.1V/s

1…5V

0.04V/s

Engineering Units

-10…+10V

21000

210

0.2V/s

0…5V

5750

58

0.05V/s

0…10V

11000

110

0.1V/s

1…5V

4750

48

0.04V/s

Scaled for PID

-10…+10V

16383

164

0.2V/s

0…5V

0.05V/s

0…10V

0.1V/s

1…5V

0.04V/s