Installation and Wiring 2-7

Panel Mounting

Mount the module to a panel using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.

Figure 2.3 Panel Mounting Using the Dimensional Template

Figure 2.4 Panel Mounting for the 1769-IF8 Using the Dimensional Template

132

(5.197)

122.6±0.2

(4.826±0.008)

35

(1.38)

28.5

(1.12)

Compact I/O

Compact I/O

Compact I/O

H

os

t Co

nt

ro

lle

r

Refer to host controller documentation for this dimension.

For more than 2 modules: (number of modules-1) X 35 mm (1,38 in.).

Righ

t En

d Ca

p

NOTE: All dimensions are in mm (inches).
Hole spacing tolerance: ±0.04 mm (0.016 in.).

l Mounting

H

ost

Co

nt

ro

lle

r

Refer to host controller documentation for this dimension.

Spacing for single-wide modules 35 mm (1.378 in).

NOTE: Overall hole spacing
tolerance: ±0.4 mm (0.016 in.)

Spacing for one-and-a-half-wide modules 52.5 mm (2.067 in).

Locate holes every 17.5 mm (0.689 in) to allow for a
mix of single-wide and one-and-a-half-wide modules
(e.g., 1769-OA16).