beautypg.com

1769-if4 input data file, 1769-if4 input data file -2 – Rockwell Automation 1769-OF2 Compact I/O Analog Modules User Manual

Page 52

background image

Publication 1769-UM002B-EN-P - July 2005

3-2 Module Data, Status, and Channel Configuration for the Input Modules

1769-IF4 Input Image

The 1769-IF4 input image file represents data words and status bits. Input
words 0 through 3 hold the input data that represents the value of the analog
inputs for channels 0 through 3. These data words are valid only when the
channel is enabled and there are no errors. Input words 4 and 5 hold the status
bits. To receive valid status information, the channel must be enabled.

1769-IF4 Configuration File

The configuration file contains information that you use to define the way a
specific channel functions. The configuration file is explained in more detail in
1769-IF4 Configuration Data File on page 3-4.

1769-IF4 Input Data File

The input data table lets you access analog input module read data for use in
the control program, via word and bit access. The data table structure is shown
in table below.

TIP

You can access information in the input image file using
the programming software configuration screen.

TIP

Not all controllers support program access to the
configuration file. Refer to your controller’s user manual.

Table 3.1 1769-IF4 Input Data Table

Word/Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Word 0

SGN

Analog Input Data Value Channel 0

Word 1

SGN

Analog Input Data Value Channel 1

Word 2

SGN

Analog Input Data Value Channel 2

Word 3

SGN

Analog Input Data Value Channel 3

Word 4

Not Used (Bits set to 0)

S3

S2

S1

S0

Word 5

U0

O0

U1

O1

U2

O2

U3

O3

Set to zero