1769-of8c and -of8v channel configuration -24 – Rockwell Automation 1769-OF2 Compact I/O Analog Modules User Manual
Page 106

Publication 1769-UM002B-EN-P - July 2005
4-24 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF8C and -OF8V Channel Configuration
The first two words of each eight word group in the configuration file allow
you to change the parameters of each channel independently. For example,
words 8 and 9 correspond to channel 1 while words 56 and 57 correspond to
channel 7.
Table 4.12 1769-OF8C Channel Configuration
(1)
Define
Indicate this
These bit settings
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Program (Idle) to
Fault Enable
Program (Idle)
Mode Data
Applied
(2)
0
Fault Mode
Data Applied
1
Hold for
Initialization
Disabled
0
Enabled
1
Program (Idle)
Mode
Hold Last
State
0
User-Defined
Value
1
Fault Mode
Hold Last
State
0
User-Defined
Fault Value
1
Enable Ramping
Disabled
0
Enabled
1
Enable Clamp/
Alarm Latching
Disabled
0
Enabled
1
Enable High
Clamp/ Alarm
Interrupt
Disabled
0
Enabled
1
Enable Low
Clamp/ Alarm
Interrupt
Disabled
0
Enabled
1
Enable Channel
Disabled
0
Enabled
1
(1)
Refer to the 1769-OF8C and -OF8V Output Channel Configuration table.
(2)
These functions are not supported by all controllers (e.g. MicroLogix 1500) using any configuration method. Refer to your
controller manual for details.