Publication 1769-UM002B-EN-P - July 2005

Installation and Wiring 2-11

System Wiring Guidelines

Consider the following when wiring your system:

General

• All module commons (ANLG COM) are connected in the analog

module. The analog common (ANLG COM) is not connected to earth
ground inside the module.

• Channels are not isolated from each other.
• Do not use the analog module’s NC terminals as connection points.
• To ensure optimum accuracy, limit overall cable impedance by keeping

your cable as short as possible. Locate the I/O system as close to your
sensors or actuators as your application will permit.

• Use Belden™ 8761, or equivalent, shielded wire.
• Keep shield connection to ground as short as possible.
• Under normal conditions, the drain wire and shield junction must be

connected to earth ground via a panel or DIN rail mounting screw at
the analog I/O module end.

(1)

1769-IF4 and -IF8 Input Modules

• If multiple power supplies are used with analog inputs, the power supply

commons must be connected together.

• The 1769-IF4 and -IF8 modules do not provide loop power for analog

inputs. Use a power supply that matches the input transmitter
specifications.

• Differential analog inputs are more immune to noise than single-ended

analog inputs.

• Voltages on Vin+, V/Iin-, and Iin+ of the 1769-IF4 and -IF8 modules

must be within ±10V dc of analog common.

1769-OF2, -OF8C, and -OF8V Output Modules

• Voltage outputs (Vout 0+ and Vout 1+ for 1769-OF2, Vout 0+

through Vout 7+ for 1769-OF8V) of the output modules are referenced
to ANLG COM. Load resistance for a voltage output channel must be
equal to or greater than 1K Ω.

• Current outputs (Iout 0+ and Iout 1+ for 1769-OF2, Iout 0+ through

Iout 7+ for 1769-OF8C) of the output modules source current that
returns to ANLG COM. Load resistance for a current output channel
must remain between 0 and 500 Ω.

(1)

In environments where high-frequency noise may be present, it may be necessary to directly ground cable
shields to earth at the module end and via a 0.1µF capacitor at the sensor end.