Output state, Chapter summary and what’s next – Rockwell Automation 1732E-OB8M8SR EtherNet/IP Dual Port 8-Point SOE Input and Scheduled Output Modules UM User Manual
Page 72
62
Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014
Chapter 9 Specific Features of the 1732E-OB8M8SR Scheduled Output Module
4.
Specify Fault Duration.
When active, Fault Duration has options of "Forever", "1 Second",
"2 Seconds", "5 Seconds" or "10 Seconds". Default is "Forever" or 0.
5.
Specify the Fault Final State.
Note that this is grayed out unless Hold Duration is something other than
“Forever”. When active, Fault Final State has the options, “Off ” and “On”.
Default value is Off.
6.
If communications fail in program mode, specify whether to “Leave
outputs in program mode” or “Change outputs to fault mode state”.
7.
Click OK.
Output State
The Scheduled Output module allows the user to define output state when in
Program Mode and Fault Mode.
Program Mode refers to the state where the following events occur:
• Controller program is not executing.
• Inputs are still actively producing data.
• Outputs are not actively controlled and go to their configured Program
mode.
Fault Mode selects the behavior the output channel takes if a communication
fault occurs. FaultValue defines the value to go to on fault if the bit is set.
Fault Mode provides individual fault mode selection for output channels. When
this selection is disabled [the bit is reset (0)] and the system enters the fault mode,
the module holds the last output state value. This means that the output remains
at the last converted value prior to the condition that caused the system to enter
the fault mode.
Chapter Summary and
What’s Next
In this chapter, you read about the features specific to the Scheduled Output
module. The next chapter describes using the modules.