Wire the module – Rockwell Automation 1732E-OB8M8SR EtherNet/IP Dual Port 8-Point SOE Input and Scheduled Output Modules UM User Manual
Page 29
Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014
19
Install Your Module Chapter 4
2.
Drill the necessary holes for #6 (M3) pan head screws.
3.
Mount the module using #6 (M3) screws.
Mount the Module in High Vibration Areas
If you mount the module in an area that is subject to shock or vibration, we
recommend you use a flat and a lock washer to mount the module. Mount the flat
and the lock washer as shown in the mounting illustration. Torque the mounting
screws to 0.68 Nm (6 lb-in.).
High Vibration Area Mounting
Wire the Module
The 1732E-OB8M8SR and 1732E-IB8M8SOER ArmorBlock EtherNet/IP
modules have 3-pin pico-style I/O connectors. We provide caps to cover the
unused connectors on your module. Connect the quick-disconnect cord sets you
selected for your module to the appropriate ports.
I/O Connectors
Refer to the pinout diagrams for the I/O connectors.
Pico-style 3-Pin Input Female Connector
45768
Lock washer
Flat washer
(View into connector)
Pin 1 Sensor source voltage
Pin 3 Return
Pin 4 Input
43583