C - data tables, Data tables, Communicate with your module – Rockwell Automation 1732E-OB8M8SR EtherNet/IP Dual Port 8-Point SOE Input and Scheduled Output Modules UM User Manual
Page 115: Connection points, Appendix
![background image](/manuals/579647/115/background.png)
Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014
105
Appendix
C
Data Tables
Communicate with Your
Module
Read this section for information about how to communicate with your module.
I/O messages are sent to (consumed) and received from (produced) the
ArmorBlock I/O modules. These messages are mapped into the processor or
scanner memory. The following table lists the assembly instances and connection
points for the 1732E EtherNet/IP ArmorBlock Sequence of Events Input and
Scheduled Sourcing Output Modules.
Connection Points
In the following tables, Input pertains to the produced data from the module to
the controller, and Output refers to consumed data by the module from the
controller.
Catalog Number
Connection Format
Timestamp
Module-Defined
Data Type
Assembly Instance /
Connection Point
(decimal)
1732E-IB8M8SOER
Data (default)
Per Point (default)
Configuration
111
Input
157
Output
159
Data
First In First Out
Configuration
111
Input
158
Output
159
Data
None
Configuration
111
Input
104
Output
191
Listen Only
None
Configuration
189
Input
104
Output
191
1732E-OB8M8SR
(1)
Per Point
Configuration
171
Input
177
Output
174
None
Configuration
171
Input
191
Output
34