B - module tags, Module tags, Module tag names and definitions – Rockwell Automation 1732E-OB8M8SR EtherNet/IP Dual Port 8-Point SOE Input and Scheduled Output Modules UM User Manual
Page 107: Tags used, Appendix
![background image](/manuals/579647/107/background.png)
Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014
97
Appendix
B
Module Tags
Fault and Status Reporting
Between the Module
and Controllers
The 1732E ArmorBlock EtherNet/IP Dual Port 8-Point Sequence of Events
Input and Scheduled Output Modules modules send fault/status data to the
owner-controller. The module maintains a Module Fault Word, the highest level
of fault reporting.
The following table describes the tag that can be examined in ladder logic to
indicate when a fault has occurred for your module:
• If a communication fault occurs on the module, all 32 bits in the Module
Fault Word are set to 1.
Module Tag Names and
Definitions
The 1732E-IB8M8SOER and 1732E-OB8M8SR has three sets of tags:
• Configuration
• Input
• Output
Tags Used
Configuration, Input and Output Tags for 1732E-IB8M8SOER
The following table describes the configuration tags generated in RSLogix 5000
software when you use your 1732E-IB8M8SOER module.
Tag
Description
Module Fault Word
This word provides fault summary reporting. The tag name is Fault.
Module Fault Word
42676
Bit 31
Bit 0
A communications fault sets all bits in the Module Fault Word.
Configuration Tags – 1732E-IB8M8SOER
Tag Name
Type
Description
C
.
FilterOffOn
INT
Sets the OFF to ON filter time for all 8 inputs. Times are set in
µs increments of 0, 1000 (default),
2000, 4000, 8000 and 16000
µs.
0 = no filtering
For more information on Software Configurable Input Filters, see
.