Rockwell Automation 1732E-OB8M8SR EtherNet/IP Dual Port 8-Point SOE Input and Scheduled Output Modules UM User Manual
Page 121
Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014
111
Data Tables Appendix C
Where:
FIFO Mode
EventAck – The controller writes back the EventNumber read to transition buffers. All events with EventNumbers less than or
equal to the EventAck will be acknowledged. If the RetreiveByPoint bit is set the PointToRetrieve attribute must also be used to
specify the point to retrieve next.
NewDataAck – Forces NewData bits clear even if all the timestamps for that point have not been acknowledged. Also clears
the EventOv bits.
PointToRetrieve – When RetrieveByPoint is set, determines point requested for events to be returned. Allows a user to query
events in the sequence they happened by point instead of the overall sequence the events occurred.
RetrieveByPoint – Changes retrieval mechanism from sequential (when 0) to retrieving events on a per point basis according
to value set in PointToRetrieve field.
Per Point Mode
EventAck – Is a 0 or 1 to indicate acknowledging an OnOff or OffOn event respectively, or a 2 to acknowledge both.
NewDataAck – Acknowledges the corresponding inputs timestamp and clears its NewData and EventOv bits.
PointToRetrieve – Not used.
RetrieveByPoint – Not used.
Reset Events – When transitioned from 0 to 1, erases all recorded time stamped events.
Configuration Assembly Instance 163 Data Structure
Consumed
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
4
Group 0 Input OFF_ON Delay Filter (Low Byte)
5
Group 0 Input OFF_ON Delay Filter (High Byte)
6
Group 0 Input ON_OFF Delay Filter (Low Byte)
7
Group 0 Input ON_OFF Delay Filter (High Byte)
8
Reserved (Ignored)
IV_G0
IA_G0
FV_G0
FA_G0
9
Reserved (Ignored)
Where:
FA_G0 = Fault Action Group 0 (0 = Apply Fault Value; 1= Hold Last State)
IA_G0 = Idle Action Group 0 (0 = Apply Fault Value; 1= Hold Last State)
FV_G0 = Fault Value Group 0 (0 = OFF;1 = ON)
IV_G0 = Idle Value Group 0 (0 = OFF;1 = ON)
Configuration Assembly Instance 171 Data Structure
Consumed
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved (Ignored)
CRN
1
Reserved (Ignored)
ProgTo
FaultEn
2
FaultMode
Ch7
FaultMode
Ch6
FaultMode
Ch5
FaultMode
Ch4
FaultMode
Ch3
FaultMode
Ch2
FaultMode
Ch1
FaultMode
Ch0
3
Reserved (Ignored)
4
FaultVal
Ch7
FaultVal
Ch6
FaultVal
Ch5
FaultVal
Ch4
FaultVal
Ch3
FaultVal
Ch2
FaultVal
Ch1
FaultVal
Ch0
5
Reserved (Ignored)
6
FaultFinal
State Ch7
FaultFinal
State Ch6
FaultFinal
State Ch5
FaultFinal
State Ch4
FaultFinal
State Ch3
FaultFinal
State Ch2
FaultFinal
State Ch1
FaultFinal
State Ch0
7
Reserved (Ignored)
Consumed Assembly Instance 159 Data Structure
Consumed
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0