Class code 0x04 – assembly object (continued) – Rockwell Automation 1329I DeviceNet Option FRN 1.XXX User Manual
Page 69

DeviceNet Objects
C-7
Class Code 0x04 –
Assembly Object
(Continued)
Instance Data Format: Output Assemblies (Continued)
(1)
If speed references are outside of their min/max limits, the drive ignores them and previous speed reference
will be maintained.
(2)
0 = 0 Hz, 1200 = 120.0 Hz.
The following table defines the possible settings of the Preset bits in
Instance 106.
The following table indicates the I/O Assembly Data Attribute mapping for
Output Assemblies.
Instance 106 Data Format (Preset Control with Speed)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault Reset RunRev
RunFwd
1
Preset 2
Preset 1
Preset 0
2
(1)
Speed Ref Hz (0.1 Hz) (Low Byte)
(2)
3
(1)
Speed Ref Hz (0.1 Hz) (High Byte)
(2)
Preset 2 Preset 1 Preset 0 Source of Speed Reference
0
0
0
Speed Ref Hz (bytes 2 and 3 of the output assembly)
0
0
1
Parameter 51 - [Preset 1]
0
1
0
Parameter 52 - [Preset 2]
0
1
1
Parameter 53 - [Preset 3]
1
0
0
Parameter 54 - [Preset 4]
1
0
1
Parameter 55 - [Preset 5]
1
1
0
Parameter 56 - [Preset 6]
1
1
1
Parameter 57 - [Preset 7]
Data Component
Name
Class
Instance
Number
Attribute
Name
Number
Name
Number
RunFwd
Supervisor
0x29
1
Run 1
3
RunRev
Supervisor
0x29
1
Run 2
4
Fault Reset
Supervisor
0x29
1
Fault Reset
12
NetCtrl
Supervisor
0x29
1
NetCtrl
5
DN Preset Cmd
Supervisor
0x29
1
DNet Preset Command
102
NetRef
AC Drive
0x2A
1
Net Ref
4
Speed Ref RPM
Supervisor
0x29
1
Dnet Speed Ref RPM
103
Speed Ref Hz
Supervisor
0x29
1
Dnet Speed Ref Hz
104