Parameter list – Rockwell Automation 1329I DeviceNet Option FRN 1.XXX User Manual
Page 57
Parameters
B-3
Parameter List
#
Object
Mapping
Name and Description
Access
Rule
(1)
Units/
Range
Factory
Default
Drive Display Parameters
01
0x0F-1-1
Command Frequency
Value of the presently selected speed reference.
Get
0.1 Hz
None
02
0x0F-2-1
Output Frequency
Output frequency to the motor.
Get
0.1 Hz
None
03
0x0F-3-1
Output Voltage
Output voltage to the motor.
Get
1 Volt
None
04
0x0F-4-1
Output Current
Output current to the motor.
Get
0.1% of
Rated
Current
None
05
0x0F-5-1
Load Current
Output current to the motor due to the load.
Get
0.1% of
Rated
Current
None
06
0x0F-6-1
Bus Voltage
DC Bus voltage level.
Get
1 Volt
None
07
0x0F-7-1
Power Unit Temperature
Temperature of the 1329I unit.
Get
1 °C
None
08
0x0F-8-1
Analog Input
The value of the analog speed reference input (terminal 2 or 3 on the control signal terminal
block).
Get
0.1% of
Full Scale
None
09
0x0F-9-1
TB Input Status
The on (1) and off (0) state of the inputs to the control signal terminal block:
Get
Bits
None
10
0x0F-10-1
Last Fault
Fault number for the most recent fault.
0 = No Fault
11 = Keypad Fixed Pattern
1 = Function Loss
12 = Keypad Redundant Start
2 = Over Current
13 = TB Redundant Start
3 = Motor Overload
14 = Keypad Connect
4 = Over Voltage
15 = Under Voltage Running
5 = Under Voltage Stop
20 = DNet EEPROM Fault
6 = Over Temperature
21 = DNet Unrecoverable Fault
7 = Communication Loss
22 = No DNet Power
8 = Parameter Checksum
23 = DNet Lost I/O Connection
9 = EEPROM Drive ID
24 = DNet Forced Fault
10 = Keypad Disconnect
25 = DNet Comm Fault
for troubleshooting procedures.
Get
0 to 24
None
Drive Program Parameters
30
0x0F-30-1
Minimum Frequency
Lowest frequency that the drive will output continuously. Its value must be less that Parameter
31 - [Maximum Frequency].
Get/
Set
(2)
0 Hz to
60 Hz
0 Hz
31
0x0F-31-1
Maximum Frequency
Highest frequency that the drive will output. Its value must be greater that the value of
Parameter 30 - [Minimum Frequency].
Get/
Set
(2)
50 Hz to
120 Hz
60 Hz
(1)
Get = Read. Set = Write. Set access is allowed only if DIP switch 10 on the 1329I Integrated drive/motor is set to On (
).
(2)
The parameter can be set only when the drive is stopped.
(3)
The parameter can be set only when the 1329 Integrated drive/motor does not have an active I/O connection.
Bit 7 Bit 6 Bit 5
Bit 4 Bit 3 Bit 2
Bit 1 Bit 0
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Stop
Start
Reset
Forward/Reverse
Function Loss
RPM/Percent Load Display
Not Used
Not Used
Speed Preset 0
Speed Preset 1
Speed Preset 2
Not Used