Rockwell Automation 1329I DeviceNet Option FRN 1.XXX User Manual
Page 62
B-8
Parameters
111 0x0F-111-1 DNet SW Version
Software version of the DeviceNet option. The number is in the form of xx.yyy where xx
indicates the major revision level and yyy indicates the minor revision level.
Get
0.000 to
10.000
None
112 0x0F-112-1 COS Mask
A 16-bit mask used to enable automatic change of state messages. A 0 disables the indicated
status from causing an automatic message. A 1 enables the status. The mask is applied to
the defined input status assembly. The default value is 0xFFFF.
Get/Set
0000 0000
0000 0000
(0x00)
to
1111 1111
1111 1111
(0xFFFF)
1111 1111
1111 1111
(0xFFFF)
113 0x0F-113-1 Reset
Reset functions for the option and 1329I unit. This parameter is a command. It will be reset to
0 = Ready after the command is completed.
0 = Ready
(No action.)
1 = Reset DNet
(Resets the DeviceNet option so that new node address or data rate settings are used.)
2 = Default DNet
(Restores the parameters in the DeviceNet group to their factory-default settings.)
3 = Default Drive
(Restores the parameters in the Drive Program group to their factory-default settings.)
Get/
Set
(2)
0 to 3
0
#
Object
Mapping
Name and Description
Access
Rule
(1)
Units/
Range
Factory
Default
(1)
Get = Read. Set = Write. Set access is allowed only if DIP switch 10 on the 1329I Integrated drive/motor is set to On (
Figure 2.3
).
(2)
The parameter can be set only when the drive is stopped.
(3)
The parameter can be set only when the 1329 Integrated drive/motor does not have an active I/O connection.