Rockwell Automation 1413-ME-PEA Capacitor Bank Controller - Series B User Manual
Page 32
Publication 1413-UM001C-EN-P - May 2006
30 Installation
N7:43
Control
Word
(1)
This is the control word for the capacitor bank
controller. The first three (3) bits of the control
word is used to set the CTPT Mode. Bit 4 is used
to initiate a restore of factory defaults. This
should be treated as a momentary state. Bit 5 is
used to initiate the step size buffer. This bit should
also be treated as a momentary state. Bit 6 is
used for disabling step tolerance. The BCD value
for each bit is available for easy setup.
Examples
- CTPT Mode 2 and Disable Step Tolerance = 68
- CTPT Mode 0 and Restore Factory Defaults = 17
to initiate a restore, then 1.
- CTPT Mode 1 and Initiate Step Buffer = 34 to
initiate step buffer, then 2
43
Ext
Configuration
2
N7:44
Unbalance
Alarm Time
seco
nds
The amount of time before alarming and resetting
the Unbalance Alarm flag
44
Ext
Configuration
1
N7:45
Number of
Powermonit
or meters
The number of Powermonitor meters to include in
the aggregate kW and kVAR calculations
45
Configuration
N7:46
Number of
Capacitor
Steps
The number of capacitor steps to be controlled
46
Configuration
N7:47
Operating
Mode
The operating mode:
0 - Manual
1 - Linear
2 - Balanced
3 - Best Fit
4 - User Defined
5 - % Voltage THD
47
Configuration
N7:59
Number of
Samples
The number of kVAR samples to average together
when auto-configuring capacitor step sizes.
1 - 10
5
-
Ext
Configuration
1
(1)
Please see the Control Word table.
Control and Status Parameters
Address
Parameter
Unit
Description
Range
Default
DAT
INT
PanelView
Screen
Control Word
Bit
Parameter
BCD Value
0
CTPT Mode 0 - Normal
1
1
CTPT Mode 1 - Neutral
2
2
CTPT Mode 2 - Retro
4
3
8