Serial hmi option ethernet hmi option, Serial hmi option, Ethernet hmi option – Rockwell Automation 1413-ME-PEA Capacitor Bank Controller - Series B User Manual
Page 23
![background image](/manuals/578730/23/background.png)
Publication 1413-UM001C-EN-P - May 2006
Installation 21
Serial HMI Option
Communications settings for the PanelView 550 are factory configured
and stored on the flash memory card.
Ethernet HMI Option
This option allows the PanelView 550 terminal to connect to your
Ethernet network. It obtains data from the MicroLogix 1500 controller
through an Ethernet interface module and your local area network.
The MicroLogix 1500 controller obtains data from the Powermonitor
meters through its Channel 1 serial port, in the identical way as the
base unit and serial HMI options.
Default communications settings are factory configured.
Communications Settings
Device / Parameter
MicroLogix 1500 Controller
Chan 0
(1)
MicroLogix 1500 Controller
Chan 1
Powermonitor Meter 1
Protocol
DF1 Full Duplex
DF1 Half-duplex Master
DF1 Half-duplex Slave
(1)
Baud
19,200
19,200
(1)
19,200
(1)
Source ID / Node Address
1
0
101
Parity / Stop Bits
None / 1
None / 1
(1)
None / 1
(1)
Handshaking
None
None
(1)
None
(1)
Error Checking
CRC
CRC
(1)
CRC
(1)
(1)
Default or out-of-box settings.
PanelView 550 Configuration Settings
Device / Parameter
PanelView 550 Operator Terminal
Protocol
DF1 Full Duplex
Baud
19,200
Source ID / Node Address
2
Parity / Stop Bits
None / 1
Handshaking
None
Error Checking
CRC