Parameter descriptions – Rockwell Automation 1413-ME-PEA Capacitor Bank Controller - Series B User Manual
Page 26

Publication 1413-UM001C-EN-P - May 2006
24 Installation
Parameter Descriptions
• Wiring mode – selected to match the physical connections to
the power system
– Delta 3 CT
– Delta 2 CT
– Direct delta 3 CT
– Direct delta 2 CT
– Open delta 3 CT
– Open delta 2 CT
– Wye (default)
– Single phase
• PT (VT) primary voltage – reflects the voltage rating on the
high side of the potential/voltage transformers. Range
1…10,000,000 V, default 480
• PT (VT) secondary voltage – reflects the voltage rating on the
low side of the potential/voltage transformers. Range 1…600 V,
default 480
• CT primary current – reflects the current rating on the high
side of the phase current transformers. Range 1…10,000,000 A,
default 5. The CT secondary current is also adjustable but the
default value of 5 A is standard
• I4 primary current – reflects the current rating on the high
side of the neutral current transformer. Range and defaults are
the same as CT primary current setting
• RS-485 node number – sets the communications address on
the RS-485 network to the MicroLogix 1500 controller.
Factory-set at 101 for PM 1, must be user configured for optional
PMs 2 …4. Range 1…247, default is the Unit ID
• IP address, subnet mask, default gateway – Ethernet port
settings required for communications with the user’s local area
network
Set Parameters with the Powermonitor Display Module
The Basic Configuration table contains the configuration parameters
needed for initial setup of the Powermonitor meter in the base system.
The table and diagram below describe the basic functionality of the
Powermonitor display module.