Appendix B – CE Compliance

B-4

Control Cable

D Control wiring must use shielded cable, or

grounded metal conduit. Refer to Figure B.3
and Figure B.4.

D The shield must be connected to signal

common at both ends of the cable.

D The Common terminals (TB3-3 & 7) must be

solidly connected (and as short as possible) to
the PE terminal of the controller.

Figure B.4 – Control Connections

Control Wiring

Shielded Enclosure

= EMC Tested Shielded Cable Clamp (or Metal Conduit)

* When the control circuitry is located outside of the 160 enclosure.

TB3

L2

L1

L3

BR

BR

1 2

4 5 6

8 9 10 11

T2

TI

T3

+

Ground Tab – PE

FAULT

READY

Shielded Control

Cable

Signal
Common

Control

Cabinet *

to TB3

3

7

R

S

T

+

U

V

W

DC

DC

Low Voltage Directive 73/23/EEC
Compliance

This product complies with Low Voltage Directive
73/23/EEC when conforming with the following
installation requirements:

D Review the General Precautions section on

page 1-1, inside front cover, and other
ATTENTION statements throughout this
manual prior to installation of the controller.

D The controller is intended to be installed with

a fixed connection to the earth. The use of
residual-current-operated protective devices
(RCDs) or ground fault indicators is not
recommended. If unavoidable, the Bulletin
160 is compatible with type B RCDs only.

D The controller should be installed in an

appropriate or suitable enclosure.

Important: The conformity of this controller and
filter to any standard does not guarantee that the
entire installation will conform. Many factors can
influence the total installation and only direct
measurements can verify total conformity.