Program group, 56 [reset functions, 57 [program lock – Rockwell Automation 160 AC DRIVE SER B/FRN 5-6.XX User Manual
Page 37: 58 [internal frequency, 59 [frequency select, 60 [zero offset, P# parameter description
Chapter 5 – Parameters and Programming
5-10
Program Group
P#
Parameter Description
Min/Max
Range
Units
Factory
Default
56
[Reset Functions]
When using this parameter, the controller’s
parameters and their associated defaults are reset according to the descriptions
below:
0 = Idle State
1 = Reset defaults (restores all controller parameter settings to factory defaults).
2 = Update input mode (restores the controller to most recent programmed P46 –
[Input Mode] setting).
After the reset/update function is complete, this parameter will set itself back to a
“0”. This parameter cannot be programmed while the controller is running.
Important:
For setting “1” only, an F48 – [Reprogram Fault] will occur and must
be cleared by cycling the STOP input to the controller. Important: P46 – [Input
Mode] factory defaults to “3 wire” control. If using keypad control, change
parameter setting back to a “2” to regain program keypad control.
0 to 2
Numeric
Value
0
57
[Program Lock]
When set to a “1”, this parameter protects all controller
parameters from being changed by unauthorized personnel.
0 to 1
Numeric
Value
0
58
[Internal Frequency]
When P59 – [Frequency Select] is set to a “1”
this parameter provides the controller frequency command. This parameter will
change the frequency command in “Real time”.
Important:
Follow normal programming procedures. Once the desired
command frequency is reached the ENTER key must be pressed to store this
value to EEPROM memory. If the ESC key is used before the ENTER key, the
frequency will return to the original value following the normal accel/decel curve.
0 to 240
0.1 Hz
60.0 Hz
59
[Frequency Select]
Selects the source of the frequency command for
the controller.
Settings:
0 = external frequency command
1 = internal frequency command from P58 – [Internal Frequency].
0 to 1
Numeric
Value
0
ЙЙЙ
Й
Й
Й
ЙЙЙ
60
[Zero Offset]
Used to add or subtract any system offset to the analog
input. See P16 – [Analog Input] for additional information.
Important:
This parameter cannot be programmed while the drive is running.
–50.0 to 50.0
Numeric
Value
0%
ЙЙЙ
ЙЙЙ
=
This parameter applies only to the Analog Signal Follower model.