Program group, 46 [input mode, 47 [output configure – Rockwell Automation 160 AC DRIVE SER B/FRN 5-6.XX User Manual
Page 34: P# parameter description
![background image](/manuals/577831/34/background.png)
Chapter 5 – Parameters and Programming
5-7
Program Group
P#
Parameter Description
Min/Max
Range
Units
Factory
Default
46
[Input Mode]
Configures the TB3 control inputs for various “3 wire” or “2
wire run-fwd/run-rev control” schemes. Also enables/disables the program keypad
module input control.
Important:
This parameter cannot be programmed while
the controller is running. Also, power must be cycled or P56 – [Reset Func-
tion] must be set to “2” for the change to take effect.
Settings:
0 = “3 wire” control
1 = “2 wire” control
2 = Program Keypad Module control
3 = Momentary ‘‘Run Forward/ Run Reverse” control
4 = 2 wire “Accel/Decel” control
5 = 2 wire “Enable” control
6 = 2 wire “Local/Remote” control
See Chapter 2 for wiring diagrams and description of settings.
0 to 6
Numeric
Value
0
47
[Output Configure]
Configures the TB3 relay output functionality.
Settings
0 = Controller
Ready/Faulted
1 = At Frequency
2 = Controller Running
3 = Reverse
4 = Motor Overload
5 = Ramp Regulated
7= Above Current
6 = Above Frequency
Output changes state when...
8 = Above DC Bus
Voltage
energized and returns to shelf state when
power is removed or when a fault occurs.
the controller reaches commanded frequency.
the controller is running.
the controller is commanded to run in the reverse
direction.
when a motor overload condition exists.
the ramp regulator is modifying the
programmed accel/decel times to avoid an
overcurrent or overvoltage fault from occurring.
the controller exceeds the frequency value
set in P48 – [Output Threshold].
the controller exceeds the value set in P48 –
[Output Threshold]. Important: Value for
P48 – [Output Threshold] must be entered in
% of controller rated output current.
the controller exceeds the DC bus voltage value set
in P48 – [Output Threshold].
9 = Retries Exhausted
the number of retries for P50 – [Restart Tries] is
exceeded.
0 to 9
Numeric
Value
0