Chapter 2 – Installation and Wiring
2-5
Table 2.G – Cable Length Recommendations — Capacitive Current
380
460V
Motor Cable Only
RWR at Drive
①
Reactor at Motor
380 – 460V
Ratings
kHz
Shielded
②
Unshielded
Shielded
②
Unshielded
Shielded
②
Unshielded
Ratings
k z
ft.
m.
ft.
m.
ft.
m.
ft.
m.
ft.
m.
ft.
m.
2 2 kW
2
360
110
750
229
280
85
600
183
410
125
525
160
2.2 kW
(3 HP
4
335
102
600
183
260
79
600
183
370
113
475
145
(3 HP
8
300
91
410
125
➀
➀
➀
➀
310
94
420
128
1 5 kW
2
300
91
540
165
430
131
540
165
310
94
425
130
1.5 kW
(2 HP
4
300
91
425
130
410
125
425
130
300
91
400
122
(2 HP
8
300
91
300
91
➀
➀
➀
➀
300
91
350
107
0 75 kW
2
300
91
375
114
250
76
375
114
300
91
300
91
0.75 kW
(1 HP)
4
300
91
300
91
225
69
375
114
300
91
300
91
(1 HP)
8
300
91
300
91
➀
➀
➀
➀
300
91
300
91
0 55 kW
2
300
91
375
114
250
76
375
114
300
91
300
91
0.55 kW
(0 75 HP)
4
300
91
310
94
225
69
375
114
300
91
300
91
(0.75 HP)
8
300
91
300
91
➀
➀
➀
➀
300
91
300
91
0 37 kW
2
300
91
375
114
250
76
375
114
300
91
300
91
0.37 kW
(0 5 HP)
4
300
91
325
99
225
69
375
114
300
91
300
91
(0.5 HP)
8
300
91
300
91
➀
➀
➀
➀
300
91
300
91
200
240V
Motor Cable Only
RWR at Drive
Reactor at Motor
200 – 240V
Ratings
Shielded
Unshielded
Shielded
Unshielded
Shielded
Unshielded
Ratings
ft.
m.
ft.
m.
ft.
m.
ft.
m.
ft.
m.
ft.
m.
0.37 to 2.2 kW
(0.5 to 3 HP)
2 thru 8 kHz
500
152
800
244
③
③
③
③
500
152
800
244
➀
Not recommended for use above 4 kHz PWM frequency.
➁
When using shielded cable at lightly loaded conditions, the 0.75 Kw (1 Hp) and below cable length recommendations are 61m (200 ft.)
➂
Not recommended for 230V applications.