Display group, 01 [output frequency, 02 [output voltage – Rockwell Automation 160 AC DRIVE SER B/FRN 5-6.XX User Manual
Page 29: 03 [output current, 04 [output power, 05 [bus voltage, 06 [frequency command, 07 [last fault, 08 [heatsink temperature, 09 [controller status
![background image](/manuals/577831/29/background.png)
Chapter 5 – Parameters and Programming
5-2
Display Group Parameters
This group of parameters consists of commonly viewed controller operating conditions such as controller
output frequency, output voltage, output current and frequency command. All parameters in this group
are read only.
Important: The last user selected Display Group parameter will be saved on power down.
Display Group
P#
Parameter Description
Min/Max
Range
Units
01
[Output Frequency]
Displays the output frequency at TB2 terminals T1, T2 and
T3 (U, V and W).
0 to 240
0.1 Hz
02
[Output Voltage]
Displays the output voltage present at TB2 terminals T1, T2 and
T3 (U, V and W).
0 to [Max Voltage]
1 Volt
03
[Output Current]
Displays the output current present at TB2 terminals T1, T2 and
T3 (U, V and W).
0 to 2 Times
Controller Rated
Output Current
0.01Amps
04
[Output Power]
Displays the output power present at TB2 terminals T1, T2 and T3
(U, V and W).
0 to 2 Times Rated
Controller Output
Power
0.01 kW
05
[Bus Voltage]
Displays the DC Bus Voltage level.
0 to 400 – [230V]
0 to 800 – [460V]
1 Volt
06
[Frequency Command]
Displays the frequency that the controller is
commanded to output. This command may come from any of the frequency sources
selected by
P59 – [Frequency Select]
or from a currently selected preset frequency.
0 to 240
0.1 Hz
07
[Last Fault]
Displays the coded last fault number. If a fault is currently active (has not
been cleared) the display will flash. See Chapter 6 for fault code descriptions.
0 to 49
Numeric Value
08
[Heatsink Temperature]
Displays the temperature of the controller heatsink.
0 to 150
1 Degree C
09
[Controller Status]
Displays the status of the controller in a binary
coded format.
Bit 3
Bit 2
Bit 1
Bit 0
Running
Accel
Forward
Decel
Important:
A “0” = inactive
and a “1” = active.
0000 to 1011
Binary Number
10
[Controller Type]
Used by Rockwell Automation field service personnel.
Numeric Value
Numeric Value
11
[Control Version]
Displays version of controller firmware. Used by Rockwell
Automation field service personnel.
Fixed Value
Numeric Value