Program group, 48 [output threshold, 49 [pwm frequency – Rockwell Automation 160 AC DRIVE SER B/FRN 5-6.XX User Manual
Page 35: 50 [restart tries, 51 [restart time, 52 [db enable, P# parameter description
Chapter 5 – Parameters and Programming
5-8
Program Group
P#
Parameter Description
Min/Max
Range
Units
Factory
Default
48
[Output Threshold]
Determines the on/off point for the TB3
output relay when [P47 – Output Configure] is set to 6, 7, and 8.
Settings
6
7
8
Ranges
0 to 240 Hz
0 to 180 %
0 to 815 Volts
0 to 815
Numeric
Value
0
49
[PWM Frequency]
Carrier frequency for the PWM output waveform.
The chart below provides derating guidelines based on the PWM freq. setting.
1
2
3
4
5
6
7
8
84
86
88
90
92
94
96
98
100
% Output Current (A)
Carrier Frequency, kHz
Important:
Ignoring derating guidelines can cause reduced controller perfor-
mance.
2.0 to 8.0
0.1 kHz
4.0 kHz
50
[Restart Tries]
Maximum number of times the controller will attempt to
reset a fault.
0 to 9
Numeric
Value
0
51
[Restart Time]
Time between restart attempts.
0.5 to 300
0.1 Seconds
10.0
Seconds
52
[DB Enable]
Enables/disables external dynamic braking.
Setting “0” = Disable. Settings 1 through 100 = % duty cycle braking.
Important:
The Rockwell Automation Bulletin 160 DB Resister package is rated
for 5% duty cycle. Use of this package above 5% should not be used and voids
the UL rating of this device. When setting this parameter to a value above 5%
duty cycle the resister must be sized to avoid overheating of the resister package.
Important:
This parameter cannot be programmed while the controller is
running.
0 to 100
Numeric
Value
0