Chapter 3
Program Keypad Module
3-1
Features
The program keypad module is located on the
front panel of the controller. It features the
following:
D five keys on the module for display or
programming controller parameters
D three keys for control inputs to the controller
D directional LEDs
D a 6 digit, seven segment LED display
Display Mode
The controller always powers up in the display
mode. While in this mode you may view all read
only controller parameters, but not modify them.
Program Mode
You enter the program mode by pressing the ESC
key. While in program mode, you can edit any
programmable controller parameters. Refer to
Chapter 5 for programming steps.
Figure 3.1 – Program Keypad Module Features
The
ESCape
key allows you to
toggle between the display mode
and program mode. When in
program mode, this key also
disables the editing of a parameter
value.
The
SELect
key is only used while in
program mode. It enables the editing of
a parameter value. When you press this
key the program mode indicator flashes.
Use the
up/down
➂
arrow keys to scroll
through a list of
parameters, or increase
and decrease parameter
values. Press and hold
either key to increase
scrolling speed.
Pressing the
enter
key
while in programming
mode causes the current
value displayed to be
entered into memory. When
you press this key the
program mode indicator
remains on, but stops
flashing.
The
stop
key initiates the
motor to “Coast”, “Ramp” or
“DC Brake” to stop
depending on the setting of
P34 – [Stop Mode].
Pressing the
reverse
key causes the
motor to ramp down to 0 Hz and then
ramp up to its set speed in the opposite
direction.
➁
The
clockwise LED
illuminates constantly when
the motor rotates in forward
direction.
➀
The
counter clockwise LED
illuminates constantly when the
motor rotates in reverse direction.
➀
When the
program mode
indicator
flashes, you can edit the
parameter value. When in display
mode, the program indicator does not
display.
These four digits
display the parameter
value or fault code
number.
These two digits display the active
parameter number for both display and
program parameters, which are
designated as P## throughout this
manual.
The
start
key initiates a
start command when the
controller is programmed
for local start/stop control
(when P46 – [Input Mode]
is set to “2”).
➀
Indicates commanded direction. Actual motor rotation could be
different if motor leads are not connected properly. See
Chapter 4, Start-up for details on how to verify motor rotation.
➁
When the motor is running, pressing this key causes the
(currently illuminated) LED to flash indicating motor rotation while
decelerating to zero. The opposite LED will illuminate indicating
the commanded direction.
➂
Real time frequency adjustment can be achieved when using
P58 – [Internal Frequency].