Program group, 41 [motor overload select, 42 [motor overload current – Rockwell Automation 160 AC DRIVE SER B/FRN 5-6.XX User Manual
Page 33: 43 [current limit, 44 [dc hold time, 45 [dc hold voltage, Dc injection braking mode, Ramp to stop mode, P# parameter description

Chapter 5 – Parameters and Programming
5-6
Program Group
P#
Parameter Description
Min/Max
Range
Units
Factory
Default
41
[Motor Overload Select]
Selects the derating factor for the I
2
t over-
load function.
Min Derating
Max Derating
% Base Speed
% Base Speed
0 25 50 75100 125 150 175 200
0 25 50 75 100125 150 175 200
[Overload Current]
% of
Setting
[Overload Current]
% of
Setting
100
80
60
40
20
100
80
60
40
20
Settings:
0 = No Derating
1 = Minimum Derating
2 = Maximum Derating
100
80
60
40
20
0 25 50 75 100 125 150 175 200
% Base Speed
No Derating
[Overload Current]
% of
Setting
0 to 2
Numeric
Value
0
42
[Motor Overload Current]
Set to motor nameplate full load Amps
(FLA).
0.1 to 200%
of controller
rating
.01 Amperes
115% of
Controller
Rating
43
[Current Limit]
Maximum output current allowed before current limiting
occurs. Value set in percent of controller rated output current.
1 to 180%
of controller
rating
1 %
150%
44
[DC Hold Time]
Time that P45 – [DC Hold Voltage] will be applied to the
motor when P34 – [Stop Mode Select] is set to either “DC Injection Braking” or
“Ramp to Stop” mode.
0 to 25
0.1 Second
0 Seconds
45
[DC Hold Voltage]
DC Voltage level applied to the motor during braking
when P34 – [Stop Mode Select] is set to either “DC Injection Braking” or “Ramp
to Stop” mode.
Important:
If the current exceeds P43 – [Current Limit] the voltage applied to
the motor will be less than this setting.
0 to 115
1 Volt
0 Volts
[DC Hold Time]
y
Stop Command
[DC Hold Voltage]
Time
Speed
Voltage
Volts and Speed
DC Injection Braking Mode
Volts and Speed
y
Voltage
Stop Command
[DC Hold Time]
[DC Hold Voltage]
Time
Speed
Ramp to Stop Mode