beautypg.com

Chapter 5, Parameters and programming – Rockwell Automation 160 AC DRIVE SER B/FRN 5-6.XX User Manual

Page 28

background image

Chapter 5

Parameters and Programming

5-1

Overview of Parameters

This chapter covers both display and program parameters. Display parameters are read only (they cannot
be programmed), while program parameters can be changed to fit your motor control requirements. You
must have a Program Keypad Module to view/change display and program parameters. The table below
describes which parameters apply to the Preset Speed and Analog Signal Follower models. Refer to the
programming example below for programming instructions.

Parameter Type

Parameter Numbers

Analog Signal Follower Model

Preset Speed Model

Display

1 through 14 and 16

1 through 15

Program

30 through 60 and 69 through 76, 78

30 through 59 and 61 through 73, 78

The following pages contain descriptions of both display and program
parameters. Any parameter description that is shaded pertains only
to the Preset Speed or Analog Signal Follower model. Refer to the
legend to the right.

= Parameter applies only to the Preset Speed model

ЙЙ

ЙЙ

= Parameter applies only to the Analog Signal Follower model

Programming Example

The following is an example of the programming steps required to change a program group parameter setting. In this example,
parameter 31 – [Decel Time] is changed from its factory default setting of 10.0 seconds to 2.2 seconds. Refer to Chapter 3,
Figure 3.1 on page 3-1 for an explanation of Program Keypad Module display and programming keys.
Important: To reset ALL values to original factory default settings, refer to P56 – [Reset Defaults].

Action

Description

Keypad Display

1.

To program the value of a program group parameter, enter the
program group by pressing the ESCape key. The “program mode
indicator” will illuminate.

2.

Press up/down keys until the desired parameter displays. In this case,
press the up key until parameter 31 – [Decel Time] displays.

3.

Press the SELect key. The program mode indicator flashes indicating
that you can use the up/down keys to change the parameter
value.

4.

Change the decel time value from the factory default of 10 seconds to
2.2 seconds by pressing the down key until 2.2 displays.

Important: Continuously holding the up or down key will cause the value
to increase or decrease as long as the key is pressed.

5.

When the desired value displays, press the ENTER key. This writes
the new value to memory. The program mode indicator will stop
flashing and the display will flash once indicating that the new value
has been accepted.

Important:

If at any time (while in the program mode) you wish to abort

the editing process, press the ESCape key. The original value of the
parameter will remain unchanged and you will be exited from the program
mode.

3

0

0.

Program Mode Indicator

3

0

1.

3

0

Program Mode Indicator Flashes

1.

3

2

1.

2.

1

1

1

Program Mode Indicator
Stops Flashing

3 1.

2

0.

0.

0.

Program Mode Indicator
Stops Flashing

3

0

1.

1 0.

2.