Italiano-17

A065 [Sel. uscita anlg]

0/23

1

0

A066 [Uscita anlg alta]

0/800%

1%

100%

A067 [Tempo accel. 2]

0,0/600,0 sec

0,1 sec

20,0 sec

A068 [Tempo decel. 2]

0,1/600,0 sec

0,1 sec

20,0 sec

A069 [Freq interna]

0,0/400,0 Hz

0,1 Hz

0,0 Hz (per gli

inverter IP66,

NEMA/UL

Type 4X)

60,0 Hz (per

inverter IP20)

A070

A071

A072

A073

A074

A075

A076

A077

[Freq. predef. 0]

(1)

[Freq. predef. 1]

[Freq. predef. 2]

[Freq. predef. 3]

[Freq. predef. 4]

[Freq. predef. 5]

[Freq. predef. 6]

[Freq. predef. 7]

0,0/400,0 Hz

0,1 Hz

0,0 Hz

5,0 Hz

10,0 Hz

20,0 Hz

30,0 Hz

40,0 Hz

50,0 Hz

60,0 Hz

(1)

Per attivare [Freq predef 0] impostare il parametro P038 [Rif velocità] sull’opzione 4.

A078 [Frequenza jog]

0,0/[Frequenza max]

0,1 Hz

10,0 Hz

A079 [Accel/decel/ jog]

0,1/600,0 sec

0,1 sec

10,0 sec

A080 [Tempo freno CC]

0,0/99,9 sec

0,1 sec

0,0 sec

Impostando 99,9 sec. = Continuo

A081 [Liv freno CC]

0,0/(Ampere inverter

×

1,8)

0,1 Amp

Ampere

×

0,05

A082 [Sel resis freno d.]

0/99

0 = “Disabilitato”

1 = “Res RA norm”

2 = “No protez.”

3-99 = % ciclo di carico

0

A083 [% Curva S]

0/100%

1%

0%

(disabilitato)

N.

Parametro

Min/Max

Display/Opzioni

Valore

predefinito

Opzione

Gamma uscita

Valore di uscita

minimo

Valore di uscita massimo

[Uscita anlg alta]

Posizione

microinterruttore

0 “FreqUsc 0-10”

0-10 V

0 V = 0 Hz

P035 [Frequenza max]

0-10 V

1 “CorrUsc 0-10”

0-10 V

0 V = 0 ampere

200% FLA nominale inverter

0-10 V

2 “VoltUsc 0-10”

0-10 V

0 V = 0 Volt

120% volt uscita nominale inverter

0-10 V

3 “PotUsc 0-10”

0-10 V

0 V = 0 kW

200% potenza nominale inverter

0-10 V

4 “DatiPr 0-10”

0-10 V

0 V = 0000

65535 (FFFF esadecimali)

0-10 V

5 “FreqUsc 0-20”

0-20 mA

0 mA = 0 Hz

P035 [Frequenza max]

0-20 mA

6 “CorrUsc 0-20”

0-20 mA

0 mA = 0 ampere

200% FLA nominale inverter

0-20 mA

7 “VoltUsc 0-20”

0-20 mA

0 mA = 0 Volt

120% volt uscita nominale inverter

0-20 mA

8 “PotUsc 0-20”

0-20 mA

0 mA = 0 kW

200% potenza nominale inverter

0-20 mA

9 “DatiPr 0-20”

0-20 mA

0 mA = 0000

65535 (FFFF esadecimali)

0-20 mA

10 “FreqUsc 4-20”

4-20 mA

4 mA = 0 Hz

P035 [Frequenza max]

0-20 mA

11 “CorrUsc 4-20”

4-20 mA

4 mA = 0 ampere

200% FLA nominale inverter

0-20 mA

12 “VoltUsc 4-20”

4-20 mA

4 mA = 0 Volt

120% volt uscita nominale inverter

0-20 mA

13 “PotUsc 4-20”

4-20 mA

4 mA = 0 kW

200% potenza nominale inverter

0-20 mA

14 “DatiPr 4-20”

4-20 mA

4 mA = 0000

65535 (FFFF esadecimali)

0-20 mA

15 “CoppUsc 0-10” 0-10 V

0 V = 0 ampere

200% FLA nominale inverter

0-10 V

16 “CoppUsc 0-20” 0-20 mA

0 mA = 0 ampere

200% FLA nominale inverter

0-20 mA

17 “CoppUsc 4-20” 4-20 mA

4 mA = 0 ampere

200% FLA nominale inverter

0-20 mA

18 “Prest 0-10”

0-10 V

0 V = 0%

100,0% impostazione setpoint

0-10 V

19 “Prest 0-20”

0-20 mA

0 mA = 0%

100,0% impostazione setpoint

0-20 mA

20 “Prest 4-20”

4-20 mA

4 mA = 0%

100,0% impostazione setpoint

0-20 mA

21 “FreqMin 0-10”

0-10 V

0V = freq min.

P035 [Frequenza max]

0-10 V

22 “FreqMin 0-20”

0-20 mA

0 mA = freq min.

P035 [Frequenza max]

0-20 mA

23 “FreqMin 4-20”

4-20 mA

4 mA = freq min.

P035 [Frequenza max]

0-20 mA

Stato ingresso

di ingr dig 1

(morsetto I/O 05)

Stato ingresso

di ingr dig 2

(morsetto I/O 06)

Stato ingresso

di ingr dig 3

(morsetto I/O 07)

Sorgente della

frequenza

Parametro

di accelerazione/

decelerazione usato (2)

0

0

0

[Freq. predef. 0]

[Tempo accel. 1] / [Tempo decel. 1]

1

0

0

[Freq. predef. 1]

[Tempo accel. 1] / [Tempo decel. 1]

0

1

0

[Freq. predef. 2]

[Tempo accel. 2] / [Tempo decel. 2]

1

1

0

[Freq. predef. 3]

[Tempo accel. 2] / [Tempo decel. 2]

0

0

1

[Freq. predef. 4]

[Tempo accel. 1] / [Tempo decel. 1]

1

0

1

[Freq. predef. 5]

[Tempo accel. 1] / [Tempo decel. 1]

0

1

1

[Freq. predef. 6]

[Tempo accel. 2] / [Tempo decel. 2]

1

1

1

[Freq. predef. 7]

[Tempo accel. 2] / [Tempo decel. 2]

(2) Quando un ingresso digitale viene impostato su “Accel. 2 e decel. 2” e l’ingresso è attivo, quell’ingresso sovrascrive le

impostazioni contenute in questa tabella.

Per ulteriori informazioni sui parametri, consultare il manuale dell’utente di PowerFlex 40.