A065 [Sel. Sal. Anlg]
0/23
1
0
A066 [Sal. Anlg. Máx.]
0/800 %
1 %
100 %
A067 [Accel Time 2]
0.0/600.0 segundos
0.1 segundos
20.0 segundos
A068 [Decel Time 2]
0.1/600.0 segundos
0.1 segundos
20.0 segundos
A069 [Internal Freq]
0.0/400.0 Hz
0.1 Hz
0.0 Hz (para
variadores con
clasficicación
IP66, NEMA/UL
Tipo 4X)
60.0 Hz (para
variadores con
clasificación IP20)
A070
A071
A072
A073
A074
A075
A076
A077
[Preset Freq 0]
(1)
[Preset Freq 1]
[Preset Freq 2]
[Preset Freq 3]
[Preset Freq 4]
[Preset Freq 5]
[Preset Freq 6]
[Preset Freq 7]
0.0/400.0 Hz
0.1 Hz
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz
(1)
Para activar [Preset Freq 0] establezca P038 [Speed Reference] en la opción 4.
A078 [Jog Frequency]
0.0/[Maximum Freq]
0.1 Hz
10.0 Hz
A079 [Jog Accel/Decel]
0.1/600.0 segundos
0.1 segundos
10.0 segundos
A080 [DC Brake Time]
0.0/99.9 segundos
0.1 segundos
0.0 segundos
Una configuración de 99.9 segundos =
Continuo
A081 [DC Brake Level]
0.0/(Intens.Var
× 1.8) 0.1 Amps
Amps
× 0.05
A082 [DB Resistor Sel]
0/99
0 = “Disabled”
1 = “Normal RA Res”
2 = “NoProtection”
3–99 = % de ciclo de
servicio
0
No. Parámetro
Mín./máx.
Pantalla/opciones
Opción
predeterminada
en la fábrica
Opción
Rango de salida
Valor de salida
mínimo
Valor de salida máximo
[Sal. Anlg. Máx.]
Posición del
microinterruptor
0 “OutFreq 0–10”
0–10 V
0 V = 0 Hz
P035 [Maximum Freq]
0–10 V
1 “OutCurr 0–10”
0–10 V
0 V = 0 Amps
200 % Amp carga plena del variador
0–10 V
2 “OutVolt 0–10”
0–10 V
0 V = 0 Volts
120 % Volts salida nominal del variador 0–10 V
3 “OutPowr 0–10”
0–10 V
0 V = 0 kW
200 % Potencia nominal del variador
0–10 V
4 “TstData 0–10”
0–10 V
0 V = 0000
65535 (Hex FFFF)
0–10 V
5 “OutFreq 0–20”
0–20 mA
0 mA = 0 Hz
P035 [Maximum Freq]
0–20 mA
6 “OutCurr 0–20”
0–20 mA
0 mA = 0 Amps
200 % Amp carga plena del variador
0–20 mA
7 “OutVolt 0–20”
0–20 mA
0 mA = 0 Volts
120 % Volts salida nominal del variador 0–20 mA
8 “OutPowr 0–20”
0–20 mA
0 mA = 0 kW
200 % Potencia nominal del variador
0–20 mA
9 “TstData 0–20”
0–20 mA
0 mA = 0000
65535 (Hex FFFF)
0–20 mA
10 “OutFreq 4–20”
4–20 mA
4 mA = 0 Hz
P035 [Maximum Freq]
0–20 mA
11 “OutCurr 4–20”
4–20 mA
4 mA = 0 Amps
200 % Amp carga plena del variador
0–20 mA
12 “OutVolt 4–20”
4–20 mA
4 mA = 0 Volts
120 % Volts salida nominal del variador 0–20 mA
13 “OutPowr 4–20” 4–20 mA
4 mA = 0 kW
200 % Potencia nominal del variador
0–20 mA
14 “TstData 4–20”
4–20 mA
4 mA = 0000
65535 (Hex FFFF)
0–20 mA
15 “OutTorq 0–10”
0–10 V
0 V = 0 Amps
200 % Amp carga plena del variador
0–10 V
16 “OutTorq 0–20”
0–20 mA
0 mA = 0 Amps
200 % Amp carga plena del variador
0–20 mA
17 “OutTorq 4–20”
4–20 mA
4 mA = 0 Amps
200 % Amp carga plena del variador
0–20 mA
18 “Setpnt 0–10”
0–10 V
0 V = 0 %
Ajust 100.0 % pto ajus
0–10 V
19 “Setpnt 0–20”
0–20 mA
0 mA = 0 %
Ajust 100.0 % pto ajus
0–20 mA
20 “Setpnt 4–20”
4–20 mA
4 mA = 0 %
Ajust 100.0 % pto ajus
0–20 mA
21 “MinFreq 0–10”
0–10 V
0 V = Frec. mín.
P035 [Maximum Freq]
0–10 V
22 “MinFreq 0–20”
0–20 mA
0 mA = Frec. mín.
P035 [Maximum Freq]
0–20 mA
23 “MinFreq 4–20”
4–20 mA
4 mA = Frec. mín.
P035 [Maximum Freq]
0–20 mA
Estado de entrada
de Ent Digital 1
(Terminal de
E/S 05)
Estado de entrada
de Ent Digital 2
(Terminal de
E/S 06)
Estado de entrada
de Ent Digital 3
(Terminal de
E/S 07)
Fuente de frecuencia
Parámetro de Acel/
Decel usado(2)
0
0
0
[Preset Freq 0]
[Accel Time 1] / [Decel Time 1]
1
0
0
[Preset Freq 1]
[Accel Time 1] / [Decel Time 1]
0
1
0
[Preset Freq 2]
[Accel Time 2] / [Decel Time 2]
1
1
0
[Preset Freq 3]
[Accel Time 2] / [Decel Time 2]
0
0
1
[Preset Freq 4]
[Accel Time 1] / [Decel Time 1]
1
0
1
[Preset Freq 5]
[Accel Time 1] / [Decel Time 1]
0
1
1
[Preset Freq 6]
[Accel Time 2] / [Decel Time 2]
1
1
1
[Preset Freq 7]
[Accel Time 2] / [Decel Time 2]
(2) Cuando una entrada digital se establece en “Accel. 2 & Decel. 2”, y la entrada está activa, la entrada anula los ajustes
indicados en esta tabla.
Consulte el documento PowerFlex 40 User Manual para más información sobre parámetros.