Español-19 – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual
Page 111

Español-19
A111 [Anlg In 0–10 V Hi]
0.0/100.0 %
0.1 %
100.0 %
A112 [Anlg In 4–20 mA Lo] 0.0/100.0 %
0.1 %
0.0 %
A113 [Anlg In 4–20 mA Hi] 0.0/100.0 %
0.1 %
100.0 %
A114 [Slip Hertz @ FLA]
0.0/10.0 Hz
0.1 Hz
2.0 Hz
A115 [Process Time Lo]
0.00/99.99
0.01
0.00
A116 [Process Time Hi]
0.00/99.99
0.01
0.00
A117 [Bus Reg Mode]
0/1
0 = “Inhabilitado”
1 = “Habilitado”
1
A118 [Current Limit 2]
0.1/(Intens.Var
× 1.8) 0.1 Amps
Amps
× 1.5
A119 [Skip Frequency]
0/400 Hz
1 Hz
0 Hz
A120 [Skip Freq Band]
0.0/30.0 Hz
0.1 Hz
0.0 Hz
A121 [Stall Fault Time]
0/5
0 = “60 Seconds”
1 = “120 Seconds”
2 = “240 Seconds”
3 = “360 Seconds”
4 = “480 Seconds”
5 = “Flt Disabled”
0
A122 [Analog In Loss]
0/6
0 = “Disabled”
1 = “Fault (F29)”
2 = “Stop”
3 = “Zero Ref”
4 = “Min Freq Ref”
5 = “Max Freq Ref”
6 = “Int Freq Ref”
0
A123 [10 V Bipolar Enbl]
0/1
0 = “Uni-Polar In”
1 = “Bi-Polar In”
0
A124 [Var PWM Disable]
0/1
0 = “Enabled”
1 = “Disabled”
0
A125 [Torque Perf Mode]
0/1
0 = “V/Hz”
1 = “Sensrls Vect”
1
A126 [Motor NP FLA]
0.1/(Intens.Var
× 2)
0.1 Amps
Intens. Nominal
A127 [Autotune]
0/2
0 = “Ready/Idle”
1 = “Static Tune”
2 = “Rotate Tune”
0
A128 [IR Voltage Drop]
0.0/230.0 VCA
0.1 VCA
Volts nomin var.
A129 [Flux Current Ref]
0.00/[Motor NP FLA]
0.01 Amps
Intens. Nominal
A130 [PID Trim Hi]
0.0/400.0
0.1
60.0
A131 [PID Trim Lo]
0.0/400.0
0.1
0.0
A132 [PID Ref Sel]
0/8
0 = “PID Disabled”
1 = “PID Setpoint”
2 = “0–0 V Input”
3 = “4–20 mA Input”
4 = “Comm Port”
5 = “Setpnt, Trim”
6 = “0–10 V, Trim”
7 = “4–20 mA, Trim”
8 = “Comm, Trim”
0
A133 [Sel realimnt PID]
0/2
0 = “0–10 V Input”
1 = “4–20 mA Input”
2 = “Comm Port”
0
A134 [PID Prop Gain]
0.00/99.99
0.01
0.01
A135 [PID Integ Time]
0.0/999.9 segundos
0.1 segundos
0.1 segundos
A136 [PID Diff Rate]
0.00/99.99 (1/seg)
0.01 (1/seg)
0.01 (1/seg)
A137 [PID Setpoint]
0.0/100.0 %
0.1 %
0.0 %
A138 [PID Deadband]
0.0/10.0 %
0.1 %
0.0 %
A139 [PID Preload]
0.0/400.0 Hz
0.1 Hz
0.0 Hz
A140-
A147
[Stp Logic 0–7]
0001/bAFF
4 Dígitos
Para obtener una lista de las opciones de dígitos,
consulte el documento PowerFlex 40 User Manual.
00F1
A150-
A157
[Stp Logic Time 0–7] 0.0/999.9 segundos
0.1 segundos
30.0 segundos
A160 [EM Brk Off Delay]
0.01/10.00 segundos
0.01 Seg
2.00 Seg
A161 [EM Brk On Delay]
0.01/10.00 segundos
0.01 Seg
2.00 Seg
A162 [MOP Reset Sel]
0/1
0 = “Zero MOP Ref”
1 = “Save MOP Ref”
1
A163 [DB Threshold]
0.0/110.0 %
0.0 %
100.0 %
A164 [Comm Write Mode] 0/1
0 = “Save”
1 = “RAM Only”
0
A165 [Anlg Loss Delay]
0.0/20.0 segundos
0.1 segundos
0.0 segundos
A166 [Analog In Filter]
0/14
1
0
A167 [PID Invert Error]
0/1
0 = “Not Inverted”
1 = “Inverted”
0
No. Parámetro
Mín./máx.
Pantalla/opciones
Opción
predeterminada
en la fábrica
Consulte el documento PowerFlex 40 User Manual para más información sobre parámetros.