Mounting considerations, Minimum mounting clearances, Ambient operating temperatures – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual
Page 4
English-2
• Mount the drive upright on a flat, vertical and level surface.
• Protect the cooling fan by avoiding dust or metallic particles.
• Do not expose to a corrosive atmosphere.
• Protect from moisture and direct sunlight.
Minimum Mounting Clearances
See Page 21 for mounting dimensions.
Ambient Operating Temperatures
Mounting Considerations
Frame
Screw Size
Screw Torque
DIN Rail
B
M4 (#8-32)
1.56-1.96 N-m (14-17 lb.-in.)
35 mm
C
M5 (#10-24)
2.45-2.94 N-m (22-26 lb.-in.)
–
B (IP66,
Type 4X) M6 (#12-24)
3.95-4.75 N-m (35-42 lb.-in.)
–
Ambient Temperature
Enclosure Rating
Minimum Mounting
Clearances
Minimum
Maximum
-10°C (14°F)
40°C (104°F)
IP20, NEMA/UL Type Open Use Mounting Option A
IP66, NEMA/UL Type 4X
Use Mounting Option A
IP30, NEMA/UL Type 1
(1)
(1)
Rating requires installation of the PowerFlex 40 IP 30, NEMA/UL Type 1 option kit.
Use Mounting Option B
50°C (122°F) IP20, NEMA/UL Type Open Use Mounting Option B
25 mm
(1.0 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
Mounting Option A
No clearance required
between drives.
Mounting Option B
Closest object that
may restrict air flow
through the drive heat
sink and chassis