Specifications, Fuses and Circuit Breakers
Drive Ratings
Catalog
Number
(1)
Output Ratings
Input Ratings
Branch Circuit Protection
Power
Dissipation
kW (HP)
Amps
Voltage
Range
kVA Amps Fuses
140M Motor
Protectors
Contactors
IP20 Open
Watts
100 - 120V AC (±10%) – 1-Phase Input, 0 - 230V 3-Phase Output
22B-V2P3x104 0.4 (0.5)
2.3
90-132
1.15 9.0
15
140M-C2E-C16 100-C12
40
22B-V5P0x104 0.75 (1.0)
5.0
90-132
2.45 20.3
35
140M-D8E-C20 100-C23
60
22B-V6P0x104 1.1 (1.5)
6.0
90-132
3.0
24.0
40
140M-F8E-C32 100-C37
80
200 - 240V AC (±10%) – 1-Phase
(2)
Input, 0 - 230V 3-Phase Output
22B-A2P3x104 0.4 (0.5)
2.3
180-264
1.15 6.0
10
140M-C2E-B63 100-C09
40
22B-A5P0x104 0.75 (1.0)
5.0
180-264
2.45 12.0
20
140M-C2E-C16 100-C12
60
22B-A8P0x104 1.5 (2.0)
8.0
180-264
4.0
18.0
30
140M-D8E-C20 100-C23
85
22B-A012x104
2.2 (3.0)
12.0
180-264
5.5
25.0
40
140M-F8E-C32 100-C37
125
200 - 240V AC (±10%) – 3-Phase Input, 0 - 230V 3-Phase Output
22B-B2P3x104 0.4 (0.5)
2.3
180-264
1.15 2.5
6
140M-C2E-B40 100-C07
40
22B-B5P0x104 0.75 (1.0)
5.0
180-264
2.45 5.7
10
140M-C2E-C10 100-C09
60
22B-B8P0x104 1.5 (2.0)
8.0
180-264
4.0
9.5
15
140M-C2E-C16 100-C12
85
22B-B012x104
2.2 (3.0)
12.0
180-264
5.5
15.5
25
140M-C2E-C16 100-C23
125
22B-B017x104
3.7 (5.0)
17.5
180-264
8.6
21.0
30
140M-F8E-C25 100-C23
180
22B-B024x104
5.5 (7.5)
24.0
180-264
11.8 26.1
40
140M-F8E-C32 100-C37
235
22B-B033x104
7.5 (10.0)
33.0
180-264
16.3 34.6
60
140M-G8E-C45 100-C60
305
380 - 480V AC (±10%) – 3-Phase
Input, 0 - 460V 3-Phase Output
22B-D1P4x104 0.4 (0.5)
1.4
342-528
1.4
1.8
3
140M-C2E-B25 100-C07
35
22B-D2P3x104 0.75 (1.0)
2.3
342-528
2.3
3.2
6
140M-C2E-B40 100-C07
50
22B-D4P0x104 1.5 (2.0)
4.0
342-528
4.0
5.7
10
140M-C2E-B63 100-C09
70
22B-D6P0x104 2.2 (3.0)
6.0
342-528
5.9
7.5
15
140M-C2E-C10 100-C09
100
22B-D010x104
4.0 (5.0)
10.5
342-528
10.3 13.0
20
140M-C2E-C16 100-C23
160
22B-D012x104
5.5 (7.5)
12.0
342-528
11.8 14.2
25
140M-D8E-C20 100-C23
175
22B-D017x104
7.5 (10.0)
17.0
342-528
16.8 18.4
30
140M-D8E-C20 100-C23
210
22B-D024x104
11.0 (15.0) 24.0
342-528
23.4 26.0
50
140M-F8E-C32 100-C43
300
460 - 600V AC (±10%) – 3-Phase
Input, 0 - 575V 3-Phase Output
22B-E1P7x104 0.75 (1.0)
1.7
414-660
2.1
2.3
6
140M-C2E-B25 100-C09
50
22B-E3P0x104 1.5 (2.0)
3.0
414-660
3.65 3.8
6
140M-C2E-B40 100-C09
70
22B-E4P2x104 2.2 (3.0)
4.2
414-660
5.2
5.3
10
140M-C2E-B63 100-C09
100
22B-E6P6x104 4.0 (5.0)
6.6
414-660
8.1
8.3
15
140M-C2E-C10 100-C09
160
22B-E9P9x104 5.5 (7.5)
9.9
414-660
12.1 11.2
20
140M-C2E-C16 100-C16
175
22B-E012x104
7.5 (10.0)
12.2
414-660
14.9 13.7
25
140M-C2E-C16 100-C23
210
22B-E019x104
11.0 (15.0) 19.0
414-660
23.1 24.1
40
140M-D8E-C25 100-C30
300
(1)
In the Catalog Numbers listed “x” represents enclosure type. Specifications are valid for all
enclosure types. IP66, NEMA/UL Type 4X drive ratings are only available as Frame B drives.
(2)
200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix
changes from N104 to N114. Filter option is not available for IP66, NEMA/UL Type 4X rated drives.