‎Chapter 4 PAS Application Software

General Meter Setup

Series PM175 Powermeters

63

The following table lists available network options.

Parameter

Options

Default

Device IP Address

192.168.0.203

Network Subnet Mask

255.255.255.0

Network Default Gateway

192.168.0.1

TCP Service Port

502 = Modbus/TCP
20000 = DNP3/TCP

502

The TCP service port can also be changed trough the COM1

serial port setup: changing the protocol for the port automatically

changes the TCP port for the Ethernet.

To change the Ethernet settings in your meter, select desired
parameters, and then click Send.

NOTES

1. The meter provides the permanent Modbus TCP server

on port 502. Selecting the DNP3 TCP service port
launches the DNP3 TCP server in addition to the Modbus
server allowing simultaneous connections on both ports.
Selecting the Modbus TCP port disables the DNP3 TCP
server.

2. When you change the device network settings through the

Ethernet port, the device port restarts so communication
will be temporarily lost. You may need to wait some

additional time until PAS restores a connection with your
device.

General Meter Setup

This section describes how to configure the PM175 for your
particular environment and application using PAS.