Chapter 4 PAS Application Software
Viewing Recorded Files
Series PM175 Powermeters
135
PAS can give you indication on whether harmonic levels in the
sampled waveforms exceed compliance limits defined by the
power quality standards or local regulations.
To review or change harmonic limits:
1. Click on the spectrum window with the right mouse button
and select “Limits…”.
2. Select a harmonics standard, or select “Custom” and
specify your own harmonic limits.
3. Check the Enabled box to visualize harmonic faults on the
spectrum graph and in harmonic tables.