‎Chapter 2 Installation

Electrical Installation

Series PM175 Powermeters

19

Terminals

+RX

16

RS-422/RS-485

POWER SUPPLY

-RX

-TX

+TX

V

N

9

6

14

13

15

11

5

V

3

8

Handle Only at

COM.1

1

Workstations

Static-Safe

COM.2

Static-Sensitive

Devices

ATTENTION

17

N/-

L/+ 12

10

9

2

1

10-16VDC

18-36VDC

36-72VDC

2

V

5

(24)

(48)

(12)

O

S/N

S

N

LOW DC

CT.

I

1A

T

DIGITAL INPUTS

90-264VAC
50/60Hz

85-290VDC

POWER SUPPLY

V

1

2

10W

O

P

ANALOG OUTPUTS

20

18 19

1

2

23

+

21 22

+

26

25

24

3

7

6

2

4

1

- 3

RELAYS

+

1

29

28

27

2

1

ANALOG INPUTS

ANALOG IN/OUT :

+1mA

-

0-20mA

4-20mA

0-1mA

+

+

-

-

-

-

CALIBRATED AT :

25 Hz

60 Hz

50 Hz

400 Hz

COM.1 :

RS-232/422/485 STANDARD

ETHERNET
MODEM

PROFIBUS

690V

OPT.U

STANDARD

CT.

5A

Figure

2-16 Terminals - Rear View

Power Source Connection

Before connecting your meter to the power source, check the
label on the back of the device to ensure that it is equipped
with the appropriate power supply.

The power source can be dedicated-fused, or from a
monitored voltage if it is within the instrument power supply
range.

AC power supply: connect the line wire to terminal 12 and the
neutral wire to terminal 10.

DC power supply: connect the positive wire to terminal 12 and
the negative wire to terminal 10.

Chassis Ground Connection

Connect the chassis ground of the device to the switchgear
earth ground using a dedicated wire greater than 2 mm

2

/14

AWG.