04 ENHANCED VARIABLE V/Hz: Achieves maximum performance for variable
torque applications . This setting may be required for high inertia fan
applications that require fast acceleration and deceleration .
05 VECTOR SPEED: Selects vector speed mode . This setting achieves
maximum performance for speed control .
06 VECTOR TORQUE: Selects vector torque mode . This setting is for
applications where torque needs to be controlled rather than speed .
NOTE
• If setting 01 or 02 is selected all parameters above 80 will be hidden . If
setting 03 or 04 is selected parameters 84, 85 and all parameters above
87 will be hidden .
• If setting 03-06 is selected the AUTO CALIBRATION (Parameter 81)
function must be performed and the appropriate motor characteristic
parameters must be programmed properly .
• If setting 06 is selected the available settings in Parameter 05 - STANDARD
REFERENCE SOURCE change . Setting 02 (normally PRESET #1),
becomes the same as setting 01 (KEYPAD) .
P81
AUTO CALIBRATION
This is used in the ENHANCED V/Hz and VECTOR modes to measure certain motor
characteristics to achieve maximum motor performance . Select setting 01 to perform the
calibration cycle on the next start command . Setting 02 cannot be selected unless the
calibration cycle has already been completed .
00 CALIBRATION NOT DONE: Drive cannot be operated in VECTOR mode if
this parameter value is 00 .
01 CALIBRATION CYCLE ENABLED: Calibration will occur on the next start
command and will take about 40 seconds to complete . Once the calibration
cycle is successfully completed, this parameter will display "02" to indicate that
the drive can run in vector mode .
02 CALIBRATION COMPLETE: The drive can be operated in vector mode .
NOTE
Prior to performing the AUTO CALIBRATION, Parameters 85-88 and 91 must
be set properly based on the motor data . Refer to Appendix B - VECTOR
MODE for more information .
P82
CURRENT LOOP P GAIN
Normally, this parameter should not require adjustment . In special cases, however, it
may need to be adjusted to optimize performance . Do not change this parameter without
consulting Lenze-AC Tech .