INPUT WIRE SIZE REQUIREMENTS
INPUT WIRE SIZE REQUIREMENTS
208/240 Vac, 1 phase
208/240 Vac, 3 phase
400/480 Vac, 3 phase
480/590 Vac, 3 phase
MODEL AWG mm2
MODEL AWG mm2
MODEL AWG mm2
MODEL AWG mm2
TF205Y
14
1 .5
TF205Y
14
1 .5
TF405
14
1 .5
TF210Y
14
1 .5
TF210(Y)
14
1 .5
TF410
14
1 .5
TF510
14
1 .5
TF215Y
12
2 .5
TF215(Y)
14
1 .5
TF415
14
1 .5
TF220Y
12
2 .5
TF220(Y)
14
1 .5
TF420
14
1 .5
TF520
14
1 .5
TF230Y
10
4 .0
TF230(Y)
12
2 .5
TF430
14
1 .5
TF530
14
1 .5
TF250
10
4 .0
TF450
14
1 .5
TF550
14
1 .5
TF275
8
6 .0
TF475
12
2 .5
TF575
14
1 .5
TF2100
8
10
TF4100
10
4 .0
TF5100
12
2 .5
7 .4
INSTALLATION ACCORDING TO EMC REQUIREMENTS
This drive can be installed to meet the European standards for Electromagnetic Compatibility
(EMC) requirements . These requirements govern the permissible electromagnetic emissions
and immunity, both radiated and conducted, of a drive system .
The EMC requirements apply to the final installation in its entirety, not to the individual
components used . Because every installation is different, the recommended installation
should follow these guidelines as a minimum . Additional equipment (such as ferrite core
absorbers on power conductors) or alternative wiring practices may be required to meet
conformance in some installations .
Filter: The input to the drive (or group of drives) must include a filter to reduce the electrical
noise reflected back to the AC Line . To meet the industrial standards set by the EU, EN 61800-
3 for conducted emissions and EN 55011 for radiated emissions to class A compliance, the
drive must be installed with an appropriate filter and a maximum motor cable length of 10m .
EMC
Compliance with EN 61800-3/A11
SM01 1
B
C
D
A
E
Installation: Shielded cable must be used for all control and power
cables and exposed wiring must be kept as short as possible .
A Screen clamps
B Control cable
C Low-capacitance motor cable
(core/core < 75 pF/m, core/screen < 150 pF/m)
D Electrically conductive mounting plate
E Filter
13