13 programming the tcf drive – Lenze TCF Series User Manual
Page 32
13
PROGRAMMING THE TCF DRIVE
The drive may be programmed by one of three methods: using the three buttons and 3-digit
LED display on the front of the drive, programming the Electronic Programming Module (EPM)
using the optional EPM Programmer, and through a serial link using serial communications .
This section describes programming the drive using the buttons and display .
NOTE
Refer to Appendix A for information on operating the TCF Series drive in
vector mode .
BUTTONS
Mode
Display
To enter the PROGRAM mode to access the parameters, press the Mode button . This will
activate the PASSWORD prompt (if the password has not been disabled) . The display will
read “00” and the upper decimal point will be blinking as shown below .
Press Mode
Display reads "00"
Upper decimal point blinks
Use the s and t buttons to scroll to the password value (the factory default password
is “225”) and press the
Mode button . Once the correct password value is entered, the
display will read "P01", which indicates that the PROGRAM mode has been accessed at
the beginning of the parameter menu (P01 is the first parameter) .
Use s and t to scroll to the
password value
Press mode to enter password
Parameter menu is accessed at
the first parameter
NOTE
If the display flashes “Er”, the password was incorrect, and the process to
enter the password must be repeated .
28